PRODUCT SPECIFICATIONS
COMPONENT PRESSURE DROPS
Model | CFM | Wet Coil | Electric | Medium EFF. | Economizer Return | |
Heat | Filters | Air Damper | ||||
|
|
| ||||
2,600 | 0.06 | 0.03 | 0.03 | 0.14 | ||
3,000 | 0.06 | 0.04 | 0.04 | 0.14 | ||
| 3,400 | 0.07 | 0.05 | 0.05 | 0.18 | |
3,600 | 0.05 | 0.05 | 0.03 | 0.14 | ||
4,000 | 0.05 | 0.06 | 0.04 | 0.14 | ||
| 4,400 | 0.05 | 0.08 | 0.04 | 0.14 |
COOLING CAPACITY DATA — PCC090-X @ 3,000 CFM
AMB. ˚F | EVAP. |
| 75 ˚F DB |
|
| 80 ˚F DB |
|
| 85˚F DB |
|
| 90 ˚F DB |
| ||||||
EAT | KW |
| MBHT | MBHS | KW |
| MBHT | MBHS | KW | MBHT | MBHS | KW | MBHT |
| MBHS | ||||
|
|
|
| ||||||||||||||||
| 61 WB | 7.6 |
| 83.8 |
| 72.1 | 7.6 |
| 85.7 |
| 84.8 | 7.7 | 90.6 |
| 90.6 | 7.7 | 95.5 |
| 95.5 |
| 64 WB | 7.7 |
| 88.7 |
| 63.3 | 7.7 |
| 88.7 |
| 77.9 | 7.7 | 90.6 |
| 90.6 | 7.7 | 95.5 |
| 95.5 |
85 | 67 WB | 7.7 |
| 94.5 |
| 54.6 | 7.7 |
| 94.5 |
| 69.2 | 7.7 | 94.5 |
| 82.8 | 7.8 | 95.5 |
| 95.5 |
| 70 WB | 7.8 |
| 100.3 |
| 45.8 | 7.8 |
| 100.3 |
| 60.4 | 7.8 | 100.3 |
| 74.0 | 7.8 | 100.3 |
| 88.7 |
| 73 WB | 7.8 |
| 106.2 |
| 37.0 | 7.8 |
| 106.2 |
| 51.6 | 7.8 | 106.2 |
| 65.3 | 7.9 | 106.2 |
| 79.9 |
| 61 WB | 7.8 |
| 81.8 |
| 71.1 | 7.9 |
| 83.8 |
| 83.8 | 8.0 | 88.7 |
| 88.7 | 8.0 | 94.5 |
| 94.5 |
| 64 WB | 8.0 |
| 86.7 |
| 62.4 | 8.0 |
| 87.7 |
| 77.0 | 8.0 | 88.7 |
| 88.7 | 8.0 | 94.5 |
| 94.5 |
90 | 67 WB | 8.1 |
| 92.5 |
| 53.6 | 8.1 |
| 92.5 |
| 68.2 | 8.1 | 92.5 |
| 82.8 | 8.1 | 94.5 |
| 94.5 |
| 70 WB | 8.1 |
| 97.4 |
| 44.8 | 8.1 |
| 97.4 |
| 59.4 | 8.1 | 98.4 |
| 74.0 | 8.2 | 98.4 |
| 87.7 |
| 73 WB | 8.2 |
| 103.3 |
| 36.0 | 8.2 |
| 103.3 |
| 50.7 | 8.2 | 105.2 |
| 64.3 | 8.4 | 103.3 |
| 78.9 |
| 61 WB | 8.2 |
| 80.9 |
| 71.1 | 8.3 |
| 82.8 |
| 82.8 | 8.3 | 87.7 |
| 87.7 | 8.4 | 93.5 |
| 93.5 |
| 64 WB | 8.3 |
| 85.7 |
| 62.4 | 8.3 |
| 85.7 |
| 76.0 | 8.3 | 87.7 |
| 87.7 | 8.4 | 93.5 |
| 93.5 |
95 | 67 WB | 8.4 |
| 90.6 |
| 53.6 | 8.4 |
| 90.6 |
| 68.2 | 8.4 | 90.6 |
| 81.8 | 8.4 | 93.5 |
| 93.5 |
| 70 WB | 8.4 |
| 96.4 |
| 44.8 | 8.4 |
| 96.4 |
| 58.5 | 8.4 | 96.4 |
| 73.1 | 8.4 | 96.4 |
| 87.7 |
| 73 WB | 8.5 |
| 101.3 |
| 35.1 | 8.5 |
| 101.3 |
| 49.7 | 8.5 | 101.3 |
| 64.3 | 8.6 | 101.3 |
| 78.9 |
| 61 WB | 8.5 |
| 78.9 |
| 70.1 | 8.6 |
| 80.9 |
| 80.9 | 8.6 | 86.7 |
| 86.7 | 8.7 | 91.6 |
| 91.6 |
| 64 WB | 8.6 |
| 83.8 |
| 61.4 | 8.6 |
| 83.8 |
| 76.0 | 8.6 | 86.7 |
| 86.7 | 8.7 | 91.6 |
| 91.6 |
100 | 67 WB | 8.7 |
| 88.7 |
| 52.6 | 8.7 |
| 88.7 |
| 67.2 | 8.7 | 88.7 |
| 80.9 | 8.7 | 91.6 |
| 91.6 |
| 70 WB | 8.8 |
| 94.5 |
| 43.8 | 8.8 |
| 94.5 |
| 58.5 | 8.8 | 94.5 |
| 72.1 | 8.8 | 94.5 |
| 85.7 |
| 73 WB | 8.9 |
| 99.4 |
| 35.1 | 9.0 |
| 99.4 |
| 48.7 | 9.0 | 99.4 |
| 63.3 | 9.0 | 99.4 |
| 77.9 |
| 61 WB | 8.9 |
| 77.0 |
| 69.2 | 8.9 |
| 79.9 |
| 79.9 | 9.0 | 84.8 |
| 84.8 | 9.1 | 89.6 |
| 89.6 |
| 64 WB | 8.9 |
| 81.8 |
| 60.4 | 8.9 |
| 81.8 |
| 75.0 | 9.0 | 84.8 |
| 84.8 | 9.1 | 89.6 |
| 89.6 |
105 | 67 WB | 9.1 |
| 86.7 |
| 51.6 | 9.1 |
| 86.7 |
| 66.3 | 9.1 | 86.7 |
| 79.9 | 9.1 | 89.6 |
| 89.6 |
| 70 WB | 9.1 |
| 91.6 |
| 42.9 | 9.1 |
| 91.6 |
| 57.5 | 9.2 | 92.5 |
| 71.1 | 9.2 | 92.5 |
| 85.7 |
| 73 WB | 9.4 |
| 98.4 |
| 34.1 | 9.4 |
| 98.4 |
| 48.7 | 9.4 | 98.4 |
| 62.4 | 9.4 | 98.4 |
| 77.0 |
NOTES: |
|
| |
1 | Capacities are gross and are based on 230, 460 operation. | AMB | Ambient Air Temperature |
| operation must be derated by 0.98. Gross capacities do not include | EAT | Entering Air Temperature |
| evaporator motor heat. | DB | Evaporator Dry Bulb EAT |
2 | kW is for entire unit | WB | Evaporator Wet Bulb EAT |
3 | See table for capacity correction factors at other than nominal CFM. | CFM | Evaporator Airflow Ft.³/min (Table 9a) |
|
| kW | 1,000 Watts |
| SHADED AREA REPRESENTS 100% SENSIBLE COOLING | MBHT | 1,000 BTU/h Total Cooling |
|
| MBHS | 00 BTU/h Sensible Cooling |
6 | www.goodmanmfg.com | |
|
|
|