Goodman Mfg 10.3 EER Component Pressure Drops, COOLING CAPACITY DATA - PCC090-X@ 3,000 CFM

Models: 10.3 EER

1 12
Download 12 pages 55.41 Kb
Page 6
Image 6
COMPONENT PRESSURE DROPS

PRODUCT SPECIFICATIONS

COMPONENT PRESSURE DROPS

Model

CFM

Wet Coil

Electric

Medium EFF.

Economizer Return

Heat

Filters

Air Damper

 

 

 

PCC090-X

2,600

0.06

0.03

0.03

0.14

3,000

0.06

0.04

0.04

0.14

 

3,400

0.07

0.05

0.05

0.18

PCC120-X

3,600

0.05

0.05

0.03

0.14

4,000

0.05

0.06

0.04

0.14

 

4,400

0.05

0.08

0.04

0.14

COOLING CAPACITY DATA PCC090-X @ 3,000 CFM

AMB. ˚F

EVAP.

 

75 ˚F DB

 

 

80 ˚F DB

 

 

85˚F DB

 

 

90 ˚F DB

 

EAT

KW

 

MBHT

MBHS

KW

 

MBHT

MBHS

KW

MBHT

MBHS

KW

MBHT

 

MBHS

 

 

 

 

 

61 WB

7.6

 

83.8

 

72.1

7.6

 

85.7

 

84.8

7.7

90.6

 

90.6

7.7

95.5

 

95.5

 

64 WB

7.7

 

88.7

 

63.3

7.7

 

88.7

 

77.9

7.7

90.6

 

90.6

7.7

95.5

 

95.5

85

67 WB

7.7

 

94.5

 

54.6

7.7

 

94.5

 

69.2

7.7

94.5

 

82.8

7.8

95.5

 

95.5

 

70 WB

7.8

 

100.3

 

45.8

7.8

 

100.3

 

60.4

7.8

100.3

 

74.0

7.8

100.3

 

88.7

 

73 WB

7.8

 

106.2

 

37.0

7.8

 

106.2

 

51.6

7.8

106.2

 

65.3

7.9

106.2

 

79.9

 

61 WB

7.8

 

81.8

 

71.1

7.9

 

83.8

 

83.8

8.0

88.7

 

88.7

8.0

94.5

 

94.5

 

64 WB

8.0

 

86.7

 

62.4

8.0

 

87.7

 

77.0

8.0

88.7

 

88.7

8.0

94.5

 

94.5

90

67 WB

8.1

 

92.5

 

53.6

8.1

 

92.5

 

68.2

8.1

92.5

 

82.8

8.1

94.5

 

94.5

 

70 WB

8.1

 

97.4

 

44.8

8.1

 

97.4

 

59.4

8.1

98.4

 

74.0

8.2

98.4

 

87.7

 

73 WB

8.2

 

103.3

 

36.0

8.2

 

103.3

 

50.7

8.2

105.2

 

64.3

8.4

103.3

 

78.9

 

61 WB

8.2

 

80.9

 

71.1

8.3

 

82.8

 

82.8

8.3

87.7

 

87.7

8.4

93.5

 

93.5

 

64 WB

8.3

 

85.7

 

62.4

8.3

 

85.7

 

76.0

8.3

87.7

 

87.7

8.4

93.5

 

93.5

95

67 WB

8.4

 

90.6

 

53.6

8.4

 

90.6

 

68.2

8.4

90.6

 

81.8

8.4

93.5

 

93.5

 

70 WB

8.4

 

96.4

 

44.8

8.4

 

96.4

 

58.5

8.4

96.4

 

73.1

8.4

96.4

 

87.7

 

73 WB

8.5

 

101.3

 

35.1

8.5

 

101.3

 

49.7

8.5

101.3

 

64.3

8.6

101.3

 

78.9

 

61 WB

8.5

 

78.9

 

70.1

8.6

 

80.9

 

80.9

8.6

86.7

 

86.7

8.7

91.6

 

91.6

 

64 WB

8.6

 

83.8

 

61.4

8.6

 

83.8

 

76.0

8.6

86.7

 

86.7

8.7

91.6

 

91.6

100

67 WB

8.7

 

88.7

 

52.6

8.7

 

88.7

 

67.2

8.7

88.7

 

80.9

8.7

91.6

 

91.6

 

70 WB

8.8

 

94.5

 

43.8

8.8

 

94.5

 

58.5

8.8

94.5

 

72.1

8.8

94.5

 

85.7

 

73 WB

8.9

 

99.4

 

35.1

9.0

 

99.4

 

48.7

9.0

99.4

 

63.3

9.0

99.4

 

77.9

 

61 WB

8.9

 

77.0

 

69.2

8.9

 

79.9

 

79.9

9.0

84.8

 

84.8

9.1

89.6

 

89.6

 

64 WB

8.9

 

81.8

 

60.4

8.9

 

81.8

 

75.0

9.0

84.8

 

84.8

9.1

89.6

 

89.6

105

67 WB

9.1

 

86.7

 

51.6

9.1

 

86.7

 

66.3

9.1

86.7

 

79.9

9.1

89.6

 

89.6

 

70 WB

9.1

 

91.6

 

42.9

9.1

 

91.6

 

57.5

9.2

92.5

 

71.1

9.2

92.5

 

85.7

 

73 WB

9.4

 

98.4

 

34.1

9.4

 

98.4

 

48.7

9.4

98.4

 

62.4

9.4

98.4

 

77.0

NOTES:

 

 

1

Capacities are gross and are based on 230, 460 operation. 208-volt

AMB

Ambient Air Temperature

 

operation must be derated by 0.98. Gross capacities do not include

EAT

Entering Air Temperature

 

evaporator motor heat.

DB

Evaporator Dry Bulb EAT

2

kW is for entire unit

WB

Evaporator Wet Bulb EAT

3

See table for capacity correction factors at other than nominal CFM.

CFM

Evaporator Airflow Ft.³/min (Table 9a)

 

 

kW

1,000 Watts

 

SHADED AREA REPRESENTS 100% SENSIBLE COOLING

MBHT

1,000 BTU/h Total Cooling

 

 

MBHS

00 BTU/h Sensible Cooling

6

www.goodmanmfg.com

SS-GPCC

 

 

 

Page 6
Image 6
Goodman Mfg 10.3 EER Component Pressure Drops, COOLING CAPACITY DATA - PCC090-X@ 3,000 CFM, Product Specifications