Goodman Mfg ANSI Z21.47CSA-2.3 Roof Curb POST-INSTALLATION Checks, Roof TOP Duct Connections

Models: ANSI Z21.47CSA-2.3

1 32
Download 32 pages 45.6 Kb
Page 7
Image 7

removal, to allow service access and to insure proper venti- lation and condenser airflow. The unit must not be installed beneath any obstruction. The unit should be installed re- mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.

INSULATED

PANELS

ROOF CURB INSTALLATION

ROOF CURB POST-INSTALLATION

CHECKS

After installation, check the top of the curb, duct connection frame and duct flanges to make sure gasket has been ap- plied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct con- nection frame. If gasket is loose, re-apply using strong weather resistant adhesive.

PROTRUSION

Inspect curb to ensure that none of the utility services (elec- tric) routed through the curb protrude above the curb.

CAUTION

IF PROTRUSIONS EXIST, DO NOT ATTEMPT TO SET UNIT ON CURB. INFORMATION SHOWN.

ROOF TOP DUCT CONNECTIONS

Install all duct connections on the unit before placing the unit on rooftop.

RIGGING DETAILS

WARNING

TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.

CAUTION

DO NOT LIFT UNITS TWO AT A TIME. PROVISIONS FOR FORKS HAVE BEEN INCLUDED IN THE UNIT BASE FRAME. MINIMUM FORK LENGTH IS 72” TO PREVENT DAMAGE TO THE UNIT.

Provisions for forks have been included in the unit base frame. No other fork locations are approved.

WARNING

TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.

Unit must be lifted by the four lifting holes located at the base frame corners.

Lifting cables should be attached to the unit with shackles.

The distance between the crane hook and the top of the unit must not be less than 60”.

Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct- work should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb Installa- tion Instructions.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.

7

Page 7
Image 7
Goodman Mfg ANSI Z21.47CSA-2.3 Roof Curb POST-INSTALLATION Checks, Roof TOP Duct Connections, Rigging Details

ANSI Z21.47CSA-2.3 specifications

Goodman Manufacturing's ANSI Z21.47/CSA 2.3 standard is pivotal in ensuring safety and performance in gas appliances and their components. This industry benchmark outlines rigorous safety regulations for residential gas conversion appliances, specifically focusing on categories like storage water heaters, pool heaters, and certain types of boilers.

One of the main features of Goodman’s offering under this standard is its emphasis on user safety. The ANSI Z21.47/CSA 2.3 certification mandates the implementation of robust safety mechanisms to prevent accidents associated with gas leaks or malfunctions. This includes enhanced safety controls and features that mitigate the risk of combustion-related incidents, ensuring peace of mind for both manufacturers and consumers.

Technologically, Goodman Mfg has integrated advanced electronic ignition systems into its products, eliminating the need for pilot lights while enhancing energy efficiency. This technology not only reduces the risk of accidental fires but also contributes to lower energy consumption, making it an environmentally friendly option. Additionally, models compliant with this standard often incorporate smart technology, allowing for remote monitoring and control. This feature further enhances user convenience and energy management, granting homeowners the ability to optimize their energy usage.

In terms of construction and design characteristics, Goodman’s appliances are built to withstand varied operating conditions. They are designed with high-quality materials that provide durability and reliability over time, essential for maintaining performance and safety. These appliances typically feature built-in corrosion protection mechanisms to prolong their lifespan, especially in humid or corrosive environments.

Moreover, Goodman’s adherence to the ANSI Z21.47/CSA 2.3 standard signifies their commitment to energy efficiency, aligning with modern-day sustainability goals. Appliances that meet this standard often exceed governmental energy efficiency mandates, making them a wise investment for consumers aiming to reduce their carbon footprint while enjoying high-performance utility.

In conclusion, Goodman Manufacturing’s adherence to ANSI Z21.47/CSA 2.3 marks a significant dedication to safety, efficiency, and innovation in the gas appliance sector. Through advanced technologies, robust safety features, and a commitment to user satisfaction, Goodman continues to set the standard for excellence in home heating and water heating solutions.