PRODUCT DESIGN

When this product is installed in the downflow installation in an unconditioned space, remove the horizontal drain pan and install the following insulation kit

AVPTC Model

Insulation Kit

 

 

1830
DPI36-42/20

 

 

3137
DPI48-61/-20
4260

 

This kit is used to prevent sweating on the vertical drain pan.

To prevent the horizontal drain pan from sweating in high humidity applications, it is recommended that a DPIH insulation accessory kit be used. NOTE: The DPIH insu- lation kit is not supplied with this product and must be purchased separately.

See following chart for the correct DPIH kit.

AVPTC Model

Insulation Kit

 

 

1830

DPIH36-42

 

 

3137

DPIH48-61

4260

 

*AVPTC is a multi-position, variable-speed air handler and is used with R-410A. The unit's blower design includes a vari- able-speed ECM motor and is compatible with heat pumps and variable-capacity cooling applications. (See note below.)

*NOTE: Factory-sealed to achieve a 2% or less leakage rate at 1.0" water gauge external duct static pressure.

Complies with the Factory-sealed Air Handling Credit as listed in the 2001 Florida Building Code, Chapter 13, Section 610.2.A.2.1.