Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode)

Model and

 

Circuit #1

Circuit #2

Single-Point Kit

Actual kW /

Heat Kit Usage

 

MCA¹

MOP²

MCA¹

MOP²

MCA¹

MOP²

BTU@ 240V

GPC1424H41**

 

1.9

---

---

---

--

--

 

---

HKR-05*, HKR-05C*

 

21 / 25

25 / 25

---

---

24 / 27

30 / 30

4.75

/ 16,200

HKR-08*, HKR-08C*

 

32 / 36

35 / 40

---

---

33 / 38

40 / 40

7 / 23,800

HKR-10*, HKR-10C*

 

43 / 49

45 / 50

---

---

45 / 51

60 / 60

9.5 / 32,400

 

 

 

 

 

 

 

 

 

 

GPC1424H41D*

 

1.9

---

---

---

--

--

 

---

HKR-05*, HKR-05C*

 

21 / 25

25 / 25

---

---

29

30

4.75 / 16,200

HKR-08*, HKR-08C*

 

32 / 36

35 / 40

---

---

41

45

7 / 23,800

HKR-10*, HKR-10C*

 

43 / 49

45 / 50

---

---

54

60

9.5 / 32,400

 

 

 

 

 

 

 

 

 

 

GPC1430H41**

 

2.3

---

---

---

--

--

 

---

HKR-05*, HKR-05C*

 

21 / 25

25 / 25

---

---

24 / 27

30 / 30

4.75 / 16,200

HKR-08*, HKR-08C*

 

32 / 36

35 / 40

---

---

34 / 39

40 / 40

7 / 23,800

HKR-10*, HKR-10C*

 

43 / 49

45 / 50

---

---

45 / 52

60 / 60

9.5 / 32,400

HKP-15C*

 

43 / 49

45 / 50

21 / 25

25 / 25

67 / 77

70 / 80

14.25 / 48,600

 

 

 

 

 

 

 

 

 

 

GPC1430H41D*

 

2.3

---

---

---

--

--

 

---

HKR-05*, HKR-05C*

 

21 / 25

25 / 25

---

---

29

30

4.75 / 16,200

HKR-08*, HKR-08C*

 

32 / 36

35 / 40

---

---

41

45

7 / 23,800

HKR-10*, HKR-10C*

 

43 / 49

45 / 50

---

---

54

60

9.5 / 32,400

HKP-15C*

 

43 / 49

45 / 50

21 / 25

25 / 25

79

80

14.25 / 48,600

 

 

 

 

 

 

 

 

 

 

GPC1436H41**

 

2.3

---

---

---

--

--

 

---

HKR-05*, HKR-05C*

 

21 / 25

25 / 25

---

---

24 / 27

40 / 40

4.75 / 16,200

HKR-08*, HKR-08C*

 

32 / 36

35 / 40

---

---

34 / 39

40 / 40

7 / 23,800

HKR-10*, HKR-10C*

 

43 / 49

45 / 50

---

---

45 / 52

60 / 60

9.5 / 32,400

HKP-15C*

 

43 / 49

45 / 50

21 / 25

25 / 25

67 / 77

70 / 80

14.25 / 48,600

 

 

 

 

 

 

 

 

 

 

GPC1436H41D*

 

2.3

---

---

---

--

--

 

---

HKR-05*, HKR-05C*

 

21 / 25

25 / 25

---

---

29

40

4.75 / 16,200

HKR-08*, HKR-08C*

 

32 / 36

35 / 40

---

---

41

45

7 / 23,800

HKR-10*, HKR-10C*

 

43 / 49

45 / 50

---

---

54

60

9.5 / 32,400

HKP-15C*

 

43 / 49

45 / 50

21 / 25

25 / 25

79

80

14.25 / 48,600

 

 

 

 

 

 

 

 

 

 

¹ Minimum Circuit Ampacity @ 208 / 240 V

 

 

 

 

 

 

 

 

²Maximum Overcurrent Protection Device @ 208 / 240 V * Revision level that may or may not be designated

C Circuit breaker option

^ Heat Kit requires three-phase power supply

Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.