| GPC14 | GPC14 | GPC14 | GPC14 | GPC14 | GPC14 |
| 42H41C* | 42H41D* | 48H41C* | 48H41D* | 60H41C* | 60H41D* |
|
|
|
|
|
|
|
Cooling Capacity |
|
|
|
|
|
|
Cooling Capacity (BTU/h) | 40,000 | 40,000 | 46,000 | 46,000 | 57,500 | 57,500 |
Sensible BTU/h | 30,400 | 30,400 | 35,300 | 35,300 | 40,800 | 40,800 |
SEER / EER | 14.0 / 12.0 | 14.0 / 12.0 | 14.0 / 12.0 | 14.0 / 12.0 | 14.0 / 12.0 | 14.0 / 12.0 |
Decibels | 78 | 78 | 80 | 80 | 80 | 80 |
AHRI Numbers | 5677888 | 6892358 | 5677889 | 6892361 | 5677890 | 6892362 |
|
|
|
|
|
|
|
Evaporator Motor |
|
|
|
|
|
|
Type | EEM | EEM | EEM | EEM | EEM | EEM |
Wheel (D x W) | 10 x 8 | 10 x 8 | 10 x 8 | 10 x 8 | 11 x 8 | 11 x 8 |
Cooling CFM | 1,200 | 1,200 | 1,600 | 1,600 | 1,600 | 1,600 |
1,200 | 1,200 | 1,400 | 1,400 | 1,700 | 1,700 | |
RLA | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 |
No. of Speeds | 5 | 5 | 5 | 5 | 5 | 5 |
Horsepower - RPM | ½ - 1050 | ½ - 1050 | ¾ - 1050 | ¾ - 1050 | ¾ - 1050 | ¾ - 1050 |
|
|
|
|
|
|
|
Evaporator Coil |
|
|
|
|
|
|
Face Area (ft²) | 6.2 | 6.20 | 6.2 | 6.20 | 7 | 7.00 |
Rows Deep/ Fins per Inch | 4/ 14 | 4/ 14 | 4/ 14 | 4/ 14 | 4/ 14 | 4/ 14 |
Indoor Orifice Size | 0.072 | 0.072 | 0.078 | 0.078 | 0.086 | 0.086 |
Filter Size (") | (2) 20 x 20 x 1 | (2) 20 x 20 x 1 | (2) 20 x 20 x 1 | (2) 20 x 20 x 1 | (2) 20 x 25 x 1 | (2) 20 x 25 x 1 |
X | X | X | X | X | X | |
Drain Size (NPT) | ¾" | ¾" | ¾" | ¾" | ¾" | ¾" |
Refrigerant Charge (oz.) | 94 | 94 | 90 | 90 | 110 | 110 |
|
|
|
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
Horsepower - RPM | ¼ - 1075 | ¼ - 1075 | ¼ - 1075 | ¼ - 1075 | ¼ - 1075 | ¼ - 1075 |
RLA/LRA | 1.4 / 2.9 | 1.4 / 2.9 | 1.4 / 2.9 | 1.4 / 2.9 | 1.4 / 2.9 | 1.4 / 2.9 |
Fan Diameter/ # Fan Blades | 22 / 4 | 22 / 4 | 22 / 4 | 22 / 4 | 22 / 4 | 22 / 4 |
Face Area (ft²) | 16 | 16 | 19.5 | 19.5 | 17 | 17 |
Rows Deep/ Fins per Inch | 1 / 28 | 1 / 28 | 1 / 28 | 1 / 28 | 2 /28 | 2 /28 |
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
Quantity / Type | 1 / Scroll | 1 / Scroll | 1 / Scroll | 1 / Scroll | 1 / Scroll | 1 / Scroll |
Stage | Single | Single | Single | Single | Single | Single |
Compressor RLA/LRA | 17.9 / 112 | 17.9 / 112 | 19.9 / 109 | 19.9 / 109 | 26.4 / 134 | 26.4 / 134 |
|
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
|
Indoor Blower FLA | 2.9 | 3.8 | 2.9 | 5.4 | 2.9 | 5.4 |
Outdoor Fan RLA | 1.4 | 1.4 | 1.4 | 1.4 | 1.4 | 1.4 |
Total Unit Amps | 22.2 | 23.1 | 24.2 | 26.7 | 30.7 | 33.2 |
Min. Circuit Ampacity¹ | 26.6 | 28 | 29.1 | 32 | 37.3 | 40 |
Max. Overcurrent Protection (amps)² | 40 | 45 | 45 | 50 | 60 | 60 |
|
|
|
|
|
|
|
Ship Weight (lbs) | 360 | 360 | 370 | 370 | 375 | 375 |
Operating Weight (lbs) | 365 | 365 | 375 | 375 | 380 | 380 |
|
|
|
|
|
|
|
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
4 | www.goodmanmfg.com |