Heat Kit Electrical Data (Blower Only, Heat Mode)

Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode)

Model and Heat Kit Usage

 

Circuit #1

Circuit #2

Actual kW /

MCA¹

MOD²

MCA¹

MOD²

BTU@ 240V

 

 

 

 

 

 

 

 

 

GPC1424H41*

1.5

/ 1.5

--

--

--

 

--

 

 

 

 

 

 

 

 

HKR-05*, HKR-05C*

24

/ 27

30 / 30

--

--

4.75

/ 16,200

 

 

 

 

 

 

 

HKR-08*, HKR-08C*

33

/ 38

40 / 40

--

--

7 / 23,800

 

 

 

 

 

 

 

HKR-10*, HKR-10C*

45

/ 51

60 / 60

--

--

9.5 / 32,400

 

 

 

 

 

 

 

 

GPC1430H41*

2.4

/ 2.4

--

--

--

 

--

 

 

 

 

 

 

 

 

HKR-05*, HKR-05C*

24

/ 27

30 / 30

--

--

4.75

/ 16,200

 

 

 

 

 

 

 

HKR-08*, HKR-08C*

34

/ 39

40 / 40

--

--

7 / 23,800

 

 

 

 

 

 

 

HKR-10*, HKR-10C*

45

/ 52

60 / 60

--

--

9.5 / 32,400

 

 

 

 

 

 

 

HKR-15*, HKR-15C*

45

/ 52

60 / 60

22 / 25

30 / 30

14.25 / 48,600

 

 

 

 

 

 

 

 

GPC1436H41*

2.4

/ 2.4

--

--

--

 

--

 

 

 

 

 

 

 

 

HKR-05*, HKR-05C*

24

/ 27

30 / 30

--

--

4.75

/ 16,200

 

 

 

 

 

 

 

HKR-08*, HKR-08C*

34

/ 39

40 / 40

--

--

7 / 23,800

 

 

 

 

 

 

 

HKR-10*, HKR-10C*

45

/ 52

60 / 60

--

--

9.5 / 32,400

 

 

 

 

 

 

 

HKR-15*, HKR-15C*

45

/ 52

60 / 60

22 / 25

30 / 30

14.25 / 48,600

 

 

 

 

 

 

 

 

GPC1442H41*

3.9

/ 3.9

--

--

--

 

--

 

 

 

 

 

 

 

HKR-05*, HKR-05C*

25

/ 27

30 / 30

--

--

4.75 / 16,200

 

 

 

 

 

 

 

HKR-08*, HKR-08C*

34

/ 39

40 / 40

--

--

7 / 23,800

 

 

 

 

 

 

 

HKR-10*, HKR-10C*

46

/ 52

60 / 60

--

--

9.5 / 32,400

 

 

 

 

 

 

 

HKR-15*, HKR-15C*

46

/ 52

60 / 60

22 / 25

30 / 30

14.25 / 48,600

 

 

 

 

 

 

 

HKR-20*,HKR-20C*

46

/ 52

60 / 60

43 / 49

60 / 60

19.5 / 66,500

 

 

 

 

 

 

 

 

GPC1448H41*

3.9

/ 3.9

--

--

--

 

--

 

 

 

 

 

 

 

HKR-05*, HKR-05C*

25

/ 28

30 / 30

--

--

4.75 / 16,200

 

 

 

 

 

 

 

HKR-08*, HKR-08C*

34

/ 40

40 / 40

--

--

7 / 23,800

 

 

 

 

 

 

 

HKR-10*, HKR-10C*

46

/ 53

60 / 60

--

--

9.5 / 32,400

 

 

 

 

 

 

 

HKR-15*, HKR-15C*

46

/ 52

60 / 60

22 / 25

30 / 30

14.25 / 48,600

 

 

 

 

 

 

 

HKR-20*,HKR-20C*

46

/ 52

60 / 60

43 / 49

60 / 60

19.5 / 66,500

 

 

 

 

 

 

 

 

GPC1460H41*

6.0

/ 6.0

--

--

--

 

--

 

 

 

 

 

 

 

HKR-05*, HKR-05C*

26

/ 30

30 / 30

--

--

4.75 / 16,200

 

 

 

 

 

 

 

HKR-08*, HKR-08C*

36

/ 40

40 / 40

--

--

7 / 23,800

 

 

 

 

 

 

 

HKR-10*, HKR-10C*

48

/ 54

60 / 60

--

--

9.5 / 32,400

 

 

 

 

 

 

 

HKR-15*, HKR-15C*

48

/ 54

60 / 60

22 / 25

30 / 30

14.25 / 48,600

 

 

 

 

 

 

 

HKR-20*,HKR-20C*

48

/ 54

60 / 60

43 / 49

60 / 60

19.5 / 66,500

 

 

 

 

 

 

 

 

¹ Minimum Circuit Ampacity @ 208 / 240V

² Maximum Overcurrent Protection (amps) @ 208 / 240V

* Indicates revision letter that may or may not be designated

26

www.goodmanmfg.com

SS-GPC14H