Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode)
Model and Heat Kit Usage |
| Circuit #1 | Circuit #2 | Actual kW / | ||||
MCA¹ | MOD² | MCA¹ | MOD² | BTU@ 240V | ||||
| ||||||||
|
|
|
|
|
|
|
| |
GPC1424H41* | 1.5 | / 1.5 |
| |||||
|
|
|
|
|
|
|
| |
24 | / 27 | 30 / 30 | 4.75 | / 16,200 | ||||
|
|
|
|
|
|
| ||
33 | / 38 | 40 / 40 | 7 / 23,800 | |||||
|
|
|
|
|
|
| ||
45 | / 51 | 60 / 60 | 9.5 / 32,400 | |||||
|
|
|
|
|
|
|
| |
GPC1430H41* | 2.4 | / 2.4 |
| |||||
|
|
|
|
|
|
|
| |
24 | / 27 | 30 / 30 | 4.75 | / 16,200 | ||||
|
|
|
|
|
|
| ||
34 | / 39 | 40 / 40 | 7 / 23,800 | |||||
|
|
|
|
|
|
| ||
45 | / 52 | 60 / 60 | 9.5 / 32,400 | |||||
|
|
|
|
|
|
| ||
45 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |||
|
|
|
|
|
|
|
| |
GPC1436H41* | 2.4 | / 2.4 |
| |||||
|
|
|
|
|
|
|
| |
24 | / 27 | 30 / 30 | 4.75 | / 16,200 | ||||
|
|
|
|
|
|
| ||
34 | / 39 | 40 / 40 | 7 / 23,800 | |||||
|
|
|
|
|
|
| ||
45 | / 52 | 60 / 60 | 9.5 / 32,400 | |||||
|
|
|
|
|
|
| ||
45 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |||
|
|
|
|
|
|
|
| |
GPC1442H41* | 3.9 | / 3.9 |
| |||||
|
|
|
|
|
|
| ||
25 | / 27 | 30 / 30 | 4.75 / 16,200 | |||||
|
|
|
|
|
|
| ||
34 | / 39 | 40 / 40 | 7 / 23,800 | |||||
|
|
|
|
|
|
| ||
46 | / 52 | 60 / 60 | 9.5 / 32,400 | |||||
|
|
|
|
|
|
| ||
46 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |||
|
|
|
|
|
|
| ||
46 | / 52 | 60 / 60 | 43 / 49 | 60 / 60 | 19.5 / 66,500 | |||
|
|
|
|
|
|
|
| |
GPC1448H41* | 3.9 | / 3.9 |
| |||||
|
|
|
|
|
|
| ||
25 | / 28 | 30 / 30 | 4.75 / 16,200 | |||||
|
|
|
|
|
|
| ||
34 | / 40 | 40 / 40 | 7 / 23,800 | |||||
|
|
|
|
|
|
| ||
46 | / 53 | 60 / 60 | 9.5 / 32,400 | |||||
|
|
|
|
|
|
| ||
46 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |||
|
|
|
|
|
|
| ||
46 | / 52 | 60 / 60 | 43 / 49 | 60 / 60 | 19.5 / 66,500 | |||
|
|
|
|
|
|
|
| |
GPC1460H41* | 6.0 | / 6.0 |
| |||||
|
|
|
|
|
|
| ||
26 | / 30 | 30 / 30 | 4.75 / 16,200 | |||||
|
|
|
|
|
|
| ||
36 | / 40 | 40 / 40 | 7 / 23,800 | |||||
|
|
|
|
|
|
| ||
48 | / 54 | 60 / 60 | 9.5 / 32,400 | |||||
|
|
|
|
|
|
| ||
48 | / 54 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |||
|
|
|
|
|
|
| ||
48 | / 54 | 60 / 60 | 43 / 49 | 60 / 60 | 19.5 / 66,500 | |||
|
|
|
|
|
|
|
|
¹ Minimum Circuit Ampacity @ 208 / 240V
² Maximum Overcurrent Protection (amps) @ 208 / 240V
* Indicates revision letter that may or may not be designated