PRODUCT SPECIFICATIONS
SPECIFICATIONS
|
|
|
|
|
|
Cooling Capacity |
|
|
Total BTU/h | 46,400 | 54,700 |
Sensible BTU/h | 33,300 | 39,400 |
SEER / EER | 11.9 / 10.2 | 10.9 / 9.4 |
Decibels | 80 | 80 |
Evaporator Motor |
|
|
Type | DD | DD |
Wheel (D x W) | 9 x 8 | 10 x 8 |
Nominal Cooling CFM | 1,365 | 1,693 |
No. of Speeds | 2 | 2 |
Horsepower - RPM | 1/2 - 1075 | 3/4 - 1075 |
Evaporator Coil |
|
|
Face Area (ft²) | 6.2 | 7.0 |
Rows Deep/ Fins per Inch | 4/14 | 4/14 |
Filter Size (ft²) | (2) 20 x 20 x 1 | (2) 20 x 20 x 1 |
Drain Size (NPT) | 3/4” | 3/4” |
Refrigerant Charge (oz.) | 126 | 125 |
Condenser Fan / Coil |
|
|
Horsepower - RPM | 1/4 - 1075 | 1/4 - 1075 |
Fan Diameter/ # Fan Blades | 22 / 4 | 22 / 4 |
Face Area (ft²) | 17.8 | 19.1 |
Rows Deep/ Fins per Inch | 2 / 16 | 2 / 16 |
Electrical Data |
|
|
Voltage/Phase/ Frequency | ||
Compressor RLA/LRA | 7.4 / 50 | 10.3 / 65 |
Indoor Blower FLA | 1.4 | 2.2 |
Outdoor Fan RLA | 0.8 | 1.2 |
Total Unit Amps | 8.9 | 11.4 |
Min. Circuit Ampacity ¹ | 11.5 | 16.3 |
Max. Overcurrent Protection ² | 20 amps | 20 amps |
Ship Weight (lbs) | 400 | 400 |
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.