Goodman Mfg PG 15 Secondary Limit Control Pre-OperationChecks, Gas Supply And Manifold Check

Models: PG 15

1 28
Download 28 pages 47.75 Kb
Page 13
Image 13
Secondary Limit Control

If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset.

Secondary

Control Limit

Back of Unit Gas Supply And Manifold Check

Secondary Limit Control

Pre-Operation Checks

1.Close the manual gas valve external to the unit.

2.Turn off the electrical power supply to the unit.

3.Set the room thermostat to its lowest possible setting.

4.Remove the heat exchanger door on the side of the unit by removing screws.

5.This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method.

6.Move the gas control valve switch to the OFF position. Do not force.

7.Wait five minutes to clear out any gas.

8.Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 4 of this manual. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position.

9.Replace the heat exchanger door on the side of the unit.

10. Open the manual gas valve external to the unit. 11. Turn on the electrical power supply to the unit. 12. Set the thermostat to desired setting.

Open to

Manometer

Atmosphere

Hose

 

Outlet

High Fire Regulator

Regulator

Adjust

Pressure Boss

 

Vent

Gas Supply And Manifold Check

Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.

Gas Inlet Pressure Check

Gas inlet pressure must be checked and adjusted in accordance to the type of fuel being consumed.

With Power And Gas Off:

1.Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve.

Inlet gas pressure can also be measured by removing the cap from the dripleg and installing a predrilled cap with a hose fitting.

With Power And Gas On:

2.Put unit into heating cycle and turn on all other gas consuming appliances.

 

INLET GAS PRESSURE

 

 

 

Natural

 

Min. 5.0" W.C., Max. 10.0" W.C.

 

 

 

Propane

 

Min. 11.0" W.C., Max. 13.0" W.C.

NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value Shown.

If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or consult with local utility.

Gas Line

Gas

Shutoff

Valve Gas Inlet Pressure Check

Gas Line

To Furnace

Open To

Atmosphere

Drip Leg Cap

With Fitting

Manometer Hose

Manometer

Measuring Inlet Gas Pressure

Alternate Method

Manifold Pressure Check

1Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

With Power And Gas Off:With Power And Gas On:Measuring Inlet Gas PressureManifold Pressure Check Inlet White-Rodgers Model 36G54 connected to ManometerManual backgroundManual backgroundManual backgroundManual backgroundManual background Pressure Boss

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundA

Low Fire

Regulator Adjust

2.

Turn off all electrical power to the system.

3.

Back outlet pressure test screw (inlet/outlet pressure boss)

 

out one turn (counterclockwise, not more than one turn).

4.

Attach a hose and manometer to the outlet pressure boss

 

of the valve.

5.

Turn ON the gas supply.

6.

Turn on power and energize main (M) solenoid. Do not

 

energize the HI solenoid.

 

 

High Fire

 

Coaxial Coil

Manometer

Coil Terminal (HI)

Terminal (M)

 

On/Off Switch

 

 

 

 

Common

 

 

 

Terminal (C)

White-Rodgers Model 36G54 connected to Manometer

7. Measure gas manifold pressure with burners firing. Adjust

manifold pressure using the Manifold Gas Pressure table

shown below.

13

Page 13
Image 13
Goodman Mfg PG 15 Secondary Limit Control Pre-OperationChecks, Gas Supply And Manifold Check, Gas Inlet Pressure Check