Goodman Mfg SS-CKF50 specifications Dimensions, Product Specifications

Models: SS-CKF50

1 4
Download 4 pages 63.6 Kb
Page 3
Image 3
DIMENSIONS

PRODUCT SPECIFICATIONS

SPECIFICATIONS

 

CKF24-2*

CKF36-2*

CKF36-5*

CKF48-5*

CKF60-5*

CKF70-5*

Capacities

 

 

 

 

 

 

Nominal Cooling (BTU/h)

24,600

34,000

34,000

44,000

55,000

64,000

EER¹

9.0

9.0

9.0

9.0

9.0

9.0

Decibels

76

76

78

78

80

80

Compressor

 

 

 

 

 

 

RLA

12.5

17.9

5.3

7.4

9

10.9

LRA

61

97.4

42

50

74

101

Volts

220-240

220-240

380-420

380-420

380-420

380-420

Condenser Fan Motor

 

 

 

 

 

 

Horsepower

1/4

1/4

1/4

1/4

1/4

1/3

FLA

0.9

0.9

0.8

0.8

0.8

1.2

Volts

220-240

220-240

380

380

380

380

Refrigeration System

 

 

 

 

 

 

Liquid Valve Size (“O.D.)

3/8

3/8

3/8

3/8

3/8

3/8

Suction Valve Size (“O.D.)

3/4

3/4

7/8

7/8

7/8

7/8

Valve Type

Sweat

Sweat

Sweat

Sweat

Sweat

Sweat

Refrigerant Charge

88

89

89

113

121

153

Shipped with Orifice Size

0.059

0.068

0.068

0.078

0.093

0.096

Condenser Fan / Coil

 

 

 

 

 

 

Horsepower - RPM

1/4-950

1/4-950

1/4-950

1/4-950

1/4-950

1/3-1075

Fan Diameter/ # Fan Blades

20/3

20/3

20/3

22/3

22/3

22/3

Outdoor Nominal CFM

1800

1800

1800

2400

2600

3200

Face Area (ft²)

13.3

13.3

13.3

15.6

17.1

20

Rows Deep/ Fins per Inch

1/19

1/19

1/19

1/19

1/19

1/22

Fin Type

Ripple

Ripple

Ripple

Ripple

Ripple

Ripple

Coil No. of Tubes

22

22

22

22

24

36

Coil Tube Diameter (in.)

0.375

0.375

0.375

0.375

0.375

0.375

Electrical Data

 

 

 

 

 

 

Voltage-Hz / Phase

220/240-50/1

220/240-50/1

380/415-50/3

380/415-50/3

380/415-50/3

380/415-50/3

Min. Circuit Ampacity²

16.6

23.3

7.5

10

12

14.8

Max. Overcurrent Protection (amps)³

25

40

15

15

20

20

Min / Max Volts

198/264

198/264

342/456

342/456

342/456

342/456

Power Supply Conduit Size

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

Ship Weight (lbs-[kg])

180 (82)

184 (84)

184 (84)

191 (87)

210 (95)

228 (104)

¹ Energy Efficiency Ratio

²Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.

DIMENSIONS

Model

Width

Depth

Height

 

 

 

 

CKF24-2*

26

26

29¾

CKF36-2*

26

26

29¾

CKF36-5*

26

26

29¾

CKF48-5*

29

29

29¾

CKF60-5*

29

29

32¼

CKF70-5*

29

29

38¼

SS-CKF50

3

Page 3
Image 3