Goodman Mfg SS-CPG180-240 Unit Clearances, Electrical Entrance Locations, Product Specifications

Models: SS-CPG180-240

1 20
Download 20 pages 33.54 Kb
Page 13
Image 13
Unit Clearances

Product Specifications

Unit Clearances

Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compres-

sor removal or service access, and to ensure proper ventilation and condenser airflow. Do not install the unit beneath any obstruction. Install the unit away from all building exhausts

to inhibit Ingestion of exhaust air into the unit’s fresh- air intake.

36” minimum roof overhang

Electrical Entrance Locations

12¹/₈”

3³/₅”

High-Voltage

EntranceLow-

Voltage

3⁴/₅” Entrance

SS-CPG180-240

www.goodmanmfg.com

13

Page 13
Image 13
Goodman Mfg SS-CPG180-240 dimensions Unit Clearances, Electrical Entrance Locations, Product Specifications