Roof Curb Installation — Rigging

Product Specifications

Roof Curb Installation — Rigging

Provisions for forks have been included in the unit base frame. No other fork locations are approved.

Unit must be lifted by the four lifting holes located at the base frame corners.

Lifting cables should be attached to the unit with shackles.

The distance between the crane hook and the top of the unit must not be less than 60”.

Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before set- ting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. To remove the struts, extract the sheet metal retainers and pull the struts through the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Duct-work dimensions are shown in Roof Curb Installation Instructions Manual.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower than the supply air end.

Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care to center the unit. Check for proper alignment and orientation of supply and return openings with duct.

40”

 

Compressor 1

 

 

 

 

 

 

 

Coil

 

 

 

 

 

 

Evaporator

 

Return

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 2

58”

Corner & Center-of-Gravity Locations

15-Ton Units

Weights

(lbs.)

 

Corner Weight A

570

Corner Weight B

535

Corner Weight C

545

Corner Weight D

510

Shipping Weight

2270

Operating Weight

2155

20-Ton Units

Weights

(lbs.)

 

Corner Weight A

655

Corner Weight B

535

Corner Weight C

600

Corner Weight D

485

Shipping Weight

2390

Operating Weight

2275