Product Specifications
Specifications
Capacities
Nominal Cooling (BTU/h) | 23,600 | 33,000 | 35,000 | 40,000 | 48,000 | 53,000 | 57,000 |
|
|
|
|
|
|
|
|
EER¹ | 9.0 | 9.0 | 9.0 | 9.0 | 9.0 | 9.0 | 9.0 |
|
|
|
|
|
|
|
|
Nominal Heating (BTU/h) | 23,000 | 32,000 | 32,000 | 39,000 | 48,000 | 54,000 | 61,000 |
|
|
|
|
|
|
|
|
Decibels | 78 | 78 | 78 | 78 | 78 | 80 | 80 |
|
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
|
RLA
LRA
Volts
12.2 | 17.9 | 5.3 | 7.4 | 9.0 | 9.0 | 10.9 |
64 | 97.4 | 42 | 50 | 65.5 | 74 | 101 |
|
|
|
|
|
|
|
Condenser Fan Motor
Horsepower | ¼ | ¼ | ⅓ | ¼ | ⅓ | ⅓ | ⅓ |
|
|
|
|
|
|
|
|
FLA | 0.9 | 0.9 | 1.2 | 0.8 | 1.2 | 1.2 | 1.2 |
|
|
|
|
|
|
|
|
Volts | 380 | 380 | 380 | 380 | 380 | ||
|
|
|
|
|
|
|
|
Refrigeration System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid Valve Size (“O.D.) | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 | 3/8 |
|
|
|
|
|
|
|
|
Suction Valve Size (“O.D.) | ¾ | ¾ | ¾ | ⅞ | ⅞ | ⅞ | ⅞ |
|
|
|
|
|
|
|
|
Valve Type | Sweat | Sweat | Sweat | Sweat | Sweat | Sweat | Sweat |
|
|
|
|
|
|
|
|
Refrigerant Charge (oz.) | 72 | 110 | 110 | 131 | 137 | 138 | 167 |
|
|
|
|
|
|
|
|
Shipped with Orifice Size (in.) | 0.059 | 0.073 | 0.073 | 0.080 | 0.084 | 0.093 | 0.093 |
|
|
|
|
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Horsepower - RPM | |||||||
|
|
|
|
|
|
|
|
Fan Diameter/ # Fan Blades | 20/3 | 20/3 | 20/3 | 22/3 | 22/3 | 22/3 | 22/3 |
|
|
|
|
|
|
|
|
Outdoor Nominal CFM | 1800 | 1800 | 1800 | 2600 | 2600 | 2600 | 3200 |
|
|
|
|
|
|
|
|
Face Area (ft²) | 13.3 | 14.58 | 14.58 | 14.58 | 17 | 17 | 1 |
|
|
|
|
|
|
|
|
Rows Deep/ Fins per Inch | 1/19 | 1/19 | 1/19 | 1/19 | 1/19 | 1/22 | 1/22 |
|
|
|
|
|
|
|
|
Fin Type | Ripple | Ripple | Ripple | Ripple | Ripple | Ripple | Ripple |
|
|
|
|
|
|
|
|
Coil No. of Tubes | 22 | 24 | 24 | 24 | 24 | 36 | 36 |
|
|
|
|
|
|
|
|
Coil Tube Diameter (in.) | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 | 0.375 |
|
|
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| ||||
|
|
|
|
|
|
|
|
Min. Circuit Ampacity² | 16.2 | 23.3 | 7.9 | 10 | 12.4 | 12.4 | 14.8 |
|
|
|
|
|
|
|
|
Max. Overcurrent Protection ³ | 25 amps | 40 amps | 15 amps | 15 amps | 20 amps | 20 amps | 25 amps |
|
|
|
|
|
|
|
|
Min / Max Volts | 198/264 | 198/264 | 342/456 | 342/456 | 342/456 | 342/456 | 342/456 |
|
|
|
|
|
|
|
|
Power Supply Conduit Size | ½ or ¾ | ½ or ¾ | ½ or ¾ | ½ or ¾ | ½ or ¾ | ½ or ¾ | ½ or ¾ |
|
|
|
|
|
|
|
|
Ship Weight | 191 (87) | 206 (94) | 206 (94) | 213 (97) | 216 (98) | 248 (113) | 249 (113) |
|
|
|
|
|
|
|
|
¹ Energy Efficiency Ratio
²Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ³ Must use
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 3 |