ESPECIFICACIONES DEL PRODUCTO
DATOS DE CAPACIDAD DE ENFRIAMIENTO (CONT.)
TABLA 2B: PGB120245-5 (UNIDADES INGLESAS)
Aire de |
|
|
|
|
| Temperatura del Aire del Condensador |
|
|
|
|
| ||||||
Interior |
| 75°F |
|
| 85°F |
|
| 95°F |
|
| 105°F |
|
| 115°F |
| ||
SCFM | WB | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | |
KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | ||||||||
| 72 | 149.0 | 71.7 | 9.95 | 140.0 | 66.6 | 11.27 | 131.1 | 61.5 | 12.59 | 122.1 | 56.4 | 13.91 | 113.1 | 51.3 | 15.23 | |
3400 | 67 | 137.5 | 86.8 | 9.31 | 128.6 | 82.2 | 10.59 | 119.8 | 77.6 | 11.86 | 111.0 | 73.0 | 13.14 | 102.1 | 68.4 | 14.41 | |
62 | 125.1 | 106.6 | 8.89 | 119.0 | 99.7 | 10.07 | 113.0 | 92.8 | 11.25 | 106.9 | 85.9 | 12.43 | 100.9 | 79.0 | 13.61 | ||
| |||||||||||||||||
| 57 | 120.9 | 115.5 | 8.54 | 114.1 | 106.4 | 9.78 | 107.3 | 97.2 | 11.01 | 100.5 | 88.1 | 12.24 | 93.7 | 79.0 | 13.47 | |
| 72 | 155.4 | 79.5 | 10.28 | 145.7 | 74.1 | 11.62 | 136.1 | 68.7 | 12.96 | 126.4 | 63.3 | 14.30 | 116.7 | 57.9 | 15.64 | |
4000 | 67 | 142.6 | 101.8 | 9.62 | 133.7 | 95.5 | 10.92 | 124.8 | 89.2 | 12.22 | 115.9 | 82.9 | 13.52 | 107.0 | 76.6 | 14.82 | |
62 | 130.1 | 124.2 | 8.95 | 123.1 | 114.7 | 10.29 | 116.1 | 105.3 | 11.62 | 109.1 | 95.8 | 12.95 | 102.1 | 86.3 | 14.29 | ||
| |||||||||||||||||
| 57 | 130.1 | 124.2 | 8.95 | 123.1 | 114.7 | 10.29 | 116.1 | 105.3 | 11.62 | 109.1 | 95.8 | 12.95 | 102.1 | 86.3 | 14.29 | |
| 72 | 159.2 | 85.4 | 10.50 | 149.5 | 80.1 | 11.85 | 139.8 | 74.9 | 13.20 | 130.0 | 69.6 | 14.55 | 120.3 | 64.3 | 15.90 | |
4600 | 67 | 146.4 | 114.4 | 9.86 | 137.5 | 107.2 | 11.17 | 128.5 | 100.0 | 12.48 | 119.6 | 92.7 | 13.78 | 110.6 | 85.5 | 15.09 | |
62 | 137.5 | 131.9 | 9.39 | 129.9 | 121.7 | 10.75 | 122.2 | 111.6 | 12.11 | 114.6 | 101.4 | 13.46 | 107.0 | 91.3 | 14.82 | ||
| |||||||||||||||||
| 57 | 137.5 | 131.9 | 9.39 | 129.9 | 121.7 | 10.75 | 122.2 | 111.6 | 12.11 | 114.6 | 101.4 | 13.46 | 107.0 | 91.3 | 14.82 |
Las capacidades de calefacción sensible indicadas se basan en aire entrante a 80ºF con bulbo seco en el serpentín evaporador. Para otras capacidades de calefac- ción sensible, restar 84 BTU/H cada 100 CFM de aire en el serpentín evaporador por cada grado por debajo de 80ºF ó sumar 84 BTU/h cada 100 CFM de aire en el evaporador por encima de 80ºF.
TABLA 3A: PGB180245-5 (UNIDADES SI)
Aire de |
|
|
|
|
| Temperatura del Aire del Condensador |
|
|
|
|
| ||||||
Interior |
| 23.9°C |
|
| 29.4°C |
|
| 35.0°C |
|
| 40.6°C |
|
| 46.1°C |
| ||
L/S | WB | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | Cap. | Cap. | kW | |
Total | Sens | Total | Sens | Total | Sens | Total | Sens | Total | Sens | ||||||||
|
|
|
|
|
|
| |||||||||||
| 22.2 | 64.17 | 29.53 | 16.42 | 60.17 | 28.00 | 18.63 | 56.17 | 26.48 | 20.83 | 52.17 | 24.95 | 23.04 | 48.17 | 23.43 | 25.25 | |
2246 | 19.4 | 59.19 | 35.59 | 15.36 | 55.27 | 34.49 | 17.50 | 51.35 | 33.39 | 19.63 | 47.42 | 32.29 | 21.76 | 43.50 | 31.20 | 23.89 | |
16.7 | 53.86 | 43.83 | 14.67 | 51.14 | 41.88 | 16.64 | 48.42 | 39.93 | 18.61 | 45.69 | 37.99 | 20.59 | 42.97 | 36.04 | 22.56 | ||
| |||||||||||||||||
| 13.9 | 52.05 | 47.66 | 14.10 | 49.01 | 44.75 | 16.15 | 45.97 | 41.85 | 18.21 | 42.93 | 38.94 | 20.27 | 39.90 | 36.04 | 22.33 | |
| 22.2 | 66.90 | 32.71 | 16.97 | 62.61 | 31.14 | 19.21 | 58.31 | 29.56 | 21.45 | 54.01 | 27.99 | 23.68 | 49.71 | 26.42 | 25.92 | |
2643 | 19.4 | 61.40 | 41.82 | 15.87 | 57.44 | 40.10 | 18.05 | 53.48 | 38.39 | 20.22 | 49.53 | 36.68 | 22.40 | 45.57 | 34.96 | 24.57 | |
16.7 | 56.02 | 51.22 | 14.77 | 52.89 | 48.26 | 17.00 | 49.76 | 45.30 | 19.23 | 46.63 | 42.34 | 21.46 | 43.50 | 39.38 | 23.68 | ||
| |||||||||||||||||
| 13.9 | 56.02 | 51.22 | 14.77 | 52.89 | 48.26 | 17.00 | 49.76 | 45.30 | 19.23 | 46.63 | 42.34 | 21.46 | 43.50 | 39.38 | 23.68 | |
| 22.2 | 68.54 | 35.09 | 17.33 | 64.22 | 33.66 | 19.59 | 59.89 | 32.22 | 21.85 | 55.57 | 30.78 | 24.11 | 51.24 | 29.34 | 26.37 | |
3039 | 19.4 | 63.03 | 47.01 | 16.27 | 59.05 | 45.02 | 18.46 | 55.07 | 43.02 | 20.64 | 51.09 | 41.02 | 22.83 | 47.11 | 39.03 | 25.01 | |
16.7 | 59.20 | 54.38 | 15.49 | 55.79 | 51.20 | 17.76 | 52.38 | 48.02 | 20.03 | 48.98 | 44.84 | 22.30 | 45.57 | 41.66 | 24.57 | ||
| |||||||||||||||||
| 13.9 | 59.20 | 54.38 | 15.49 | 55.79 | 51.20 | 17.76 | 52.38 | 48.02 | 20.03 | 48.98 | 44.84 | 22.30 | 45.57 | 41.66 | 24.57 |
Las capacidades de calefacción sensible indicadas se basan en aire entrante a 26,7ºC con bulbo seco en el serpentín evaporador. Para otras capacidades de calefac- ción sensible, restar 44,32 W cada 47 L/S de aire en el serpentín evaporador por cada grado por debajo de los 26,7ºC o sumar 44,32 W cada 47 L/S de aire en el evaporador por encima de la temperatura mencionada.
TABLA 3B: PGB180245-5 (UNIDADES INGLESAS)
Aire de |
|
|
|
| Temperatura del Aire del Condensador |
|
|
|
|
| |||||||
Interior |
| 75°F |
|
| 85°F |
|
| 95°F |
|
| 105°F |
|
| 115°F |
| ||
SCFM | WB | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | Total | Sens | kW | |
KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | KBTU/h | ||||||||
| 72 | 219.0 | 100.8 | 16.42 | 205.3 | 95.6 | 18.63 | 191.7 | 90.4 | 20.83 | 178.0 | 85.1 | 23.04 | 164.4 | 79.9 | 25.25 | |
4760 | 67 | 202.0 | 121.4 | 15.36 | 188.6 | 117.7 | 17.50 | 175.2 | 113.9 | 19.63 | 161.8 | 110.2 | 21.76 | 148.4 | 106.5 | 23.89 | |
62 | 183.8 | 149.6 | 14.67 | 174.5 | 142.9 | 16.64 | 165.2 | 136.3 | 18.61 | 155.9 | 129.6 | 20.59 | 146.6 | 123.0 | 22.56 | ||
| |||||||||||||||||
| 57 | 177.6 | 162.6 | 14.10 | 167.2 | 152.7 | 16.15 | 156.9 | 142.8 | 18.21 | 146.5 | 132.9 | 20.27 | 136.1 | 123.0 | 22.33 | |
| 72 | 228.3 | 111.6 | 16.97 | 213.6 | 106.3 | 19.21 | 199.0 | 100.9 | 21.45 | 184.3 | 95.5 | 23.68 | 169.6 | 90.1 | 25.92 | |
5600 | 67 | 209.5 | 142.7 | 15.87 | 196.0 | 136.9 | 18.05 | 182.5 | 131.0 | 20.22 | 169.0 | 125.2 | 22.40 | 155.5 | 119.3 | 24.46 | |
62 | 191.1 | 174.8 | 14.77 | 180.5 | 164.7 | 17.00 | 169.8 | 154.6 | 19.23 | 159.1 | 144.5 | 21.46 | 148.4 | 134.4 | 23.68 | ||
| |||||||||||||||||
| 57 | 191.1 | 174.8 | 14.77 | 180.5 | 164.7 | 17.00 | 169.8 | 154.6 | 19.23 | 159.1 | 144.5 | 21.46 | 148.4 | 134.4 | 23.68 | |
| 72 | 233.9 | 119.7 | 17.33 | 219.1 | 114.8 | 19.59 | 204.4 | 109.9 | 21.85 | 189.6 | 105.0 | 24.11 | 174.9 | 100.1 | 26.37 | |
6440 | 67 | 215.1 | 160.4 | 16.27 | 201.5 | 153.6 | 18.46 | 187.9 | 146.8 | 20.64 | 174.3 | 140.0 | 22.83 | 160.7 | 133.2 | 25.01 | |
62 | 202.0 | 185.6 | 15.49 | 190.4 | 174.7 | 17.76 | 178.8 | 163.9 | 20.03 | 167.1 | 153.0 | 22.30 | 155.5 | 142.1 | 24.57 | ||
| |||||||||||||||||
| 57 | 202.0 | 185.6 | 15.49 | 190.4 | 174.7 | 17.76 | 178.8 | 163.9 | 20.03 | 167.1 | 153.0 | 22.30 | 155.5 | 142.1 | 24.57 |
Las capacidades de calefacción sensible indicadas se basan en aire entrante a 80ºF con bulbo seco en el serpentín evaporador. Para otras capacidades de calefac- ción sensible, restar 84 BTU/H cada 100 CFM de aire en el serpentín evaporador por cada grado por debajo de 80ºF ó sumar 84 BTU/h cada 100 CFM de aire en el evaporador por encima de 80ºF.
www.goodmanmfg.com | 11 |