Troubleshooting

Troubleshooting

Problem

Cause

Corrective Action

 

 

 

 

Wheel rubbing (inlet)

Adjust wheel.

 

Tighten wheel hub or bearing collars on shaft.

 

 

 

 

 

 

 

Tighten Sheaves on motor/fan shaft. Adjust belt tension. Align

 

V-belt drive

sheaves properly (see V-Belt Drives section). Replace worn belts

Excessive Noise

 

or sheaves.

 

Bearings

Replace defective bearing(s). Lubricate bearings.

 

Tighten collars and fasteners.

 

 

 

 

 

 

Wheel unbalance

Clean all dirt off wheel. Check wheel balance, rebalance if

 

necessary.

 

 

 

 

 

Low CFM

Fan

Check wheel for correct rotation. Increase fan speed.*

 

 

Duct system

See page 3.

 

 

 

 

High CFM

Fan

Decrease fan speed.

 

 

Duct system

Resize ductwork. Access door, filters, grilles not installed.

 

 

 

 

 

Duct system

 

Static Pressure

has more or less

Change obstructions in system. Use correction factor to adjust

Wrong

restriction than

for temperature/altitude. Resize ductwork. Change fan speed.*

 

anticipated

 

 

 

 

 

Fan

Check rotation of wheel. Reduce fan speed.

High Horsepower

 

 

Duct system

Resize ductwork. Check proper operation of face and bypass

 

dampers. Check filters and access doors.

 

 

 

Electrical supply

Check fuses/circuit breakers. Check for switches turned off or

 

disconnected. Check for correct supply voltage.

 

 

Fan Doesn’t Operate

Drive

Check for broken belts. Tighten loose pulleys.

 

 

 

 

Motor

Assure motor is correct horsepower and not tripping overload

 

protector.

 

 

 

 

 

Overheated Shaft

Lubrication

Check for excessive or insufficient grease in the bearings.

 

 

 

Replace damaged bearing. Relieve excessive belt tension. Align

Bearing

Mechanical

bearings. Check for bent shaft.

 

 

 

 

 

 

Belts

Adjust tightness of belts. Replacement belts should be a matched

 

set.

 

 

 

 

 

Excessive

System unbalance

Check alignment of shaft, motor and pulleys. Check wheel

balance, rebalance if necessary.

Vibration

 

 

 

 

Coupling

Check alignment between coupling, motor and fan shafts.

 

Any adjustments should be made per coupling manufacturer’s

 

misalignment

 

instructions. Shim only under motor.

 

 

*Always check motor amps and compare to nameplate rating. Excessive fan speed may overload the motor and result in motor failure. Do not exceed the maximum cataloged RPM of the fan.

NOTE: Always provide the unit model and serial numbers when requesting parts or service information.

Model BCSW-FRP 11

Page 11
Image 11
Greenheck Fan 474051 manual Troubleshooting, Problem, Cause, Corrective Action