Factory Set Points - continued
Resetting the drive to factory defaults
To reset the drive back to Greenheck factory defaults go to parameter
MODULATING CONTROL FOR FAN SPEED
| Parameter | Setting | ||
| V1000 | J1000 | ||
|
| |||
|
|
|
| |
Access Level | 2 | 2 | ||
VFD | 1 | 1 | ||
|
|
|
| |
Acceleration Time | 30 sec. | 30 sec. | ||
Deceleration Time | 30 sec. | 30 sec. | ||
|
|
|
| |
Carrier Frequency | 1 | 1 | ||
Ref Lower Limit | 50% | 50% | ||
|
|
|
| |
Motor Rated FLA | Motor | Motor | ||
FLA | FLA | |||
|
| |||
Terminal A1 Bias | 50% | 50% | ||
|
|
|
| |
Access Level | 0 | 0 |
multi-speed control FOR FAN SPEED
(1/3 or 1/2 speed reduction)
| Parameter | Setting | ||
|
|
| ||
| V1000 | J1000 | ||
|
| |||
Access Level | 2 | 2 | ||
|
|
|
| |
Reference Source (Frequency) | 0 | 0 | ||
VFD | 1 | 1 | ||
|
|
|
| |
Acceleration Time | 30 sec. | 30 sec. | ||
Deceleration Time | 30 sec. | 30 sec. | ||
|
|
|
| |
Carrier Frequency | 1 | 1 | ||
Frequency Reference 1 | 60 Hz | 60 Hz | ||
|
|
|
| |
Frequency Reference 2 | 40 Hz | 40 Hz | ||
Frequency Reference 3 | 30 Hz | 30 Hz | ||
|
|
|
| |
Frequency Reference 4 | 60 Hz | 60 Hz | ||
|
|
|
| |
Ref Lower Limit | 50% | 50% | ||
|
|
|
| |
Motor Rated FLA | Motor | Motor | ||
FLA | FLA | |||
|
| |||
3 | 3 | |||
(Terminal S4) | ||||
|
|
| ||
4 | 4 | |||
(Terminal S5) | ||||
|
|
| ||
5 | NA | |||
(Terminal S6) | ||||
|
|
| ||
A2 Not Used | F | NA | ||
|
|
|
| |
Access Level | 0 | 0 | ||
|
|
|
|
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 speed WHEN C02 drops below 700 PPM)
| Parameter | Setting | ||
| V1000 | J1000 | ||
|
| |||
|
|
|
| |
Access Level | 2 | 2 | ||
Reference Source (Frequency) | 0 | 0 | ||
|
|
|
| |
VFD | 1 | 1 | ||
Acceleration Time | 30 sec. | 30 sec. | ||
|
|
|
| |
Deceleration Time | 30 sec. | 30 sec. | ||
Carrier Frequency | 1 | 1 | ||
|
|
|
| |
Frequency Reference 1 | 60 Hz | 30 Hz | ||
|
|
|
| |
Frequency Reference 2 | 30 Hz | 60 Hz | ||
|
|
|
| |
Ref Lower Limit | 50% | 50% | ||
|
|
|
| |
Motor Rated FLA | Motor | Motor | ||
FLA | FLA | |||
|
| |||
A2 Not Used | F | NA | ||
Access Level | 0 | 0 | ||
|
|
|
|
Variable Frequency Drives for Energy Recovery Wheel
Optional factory installed VFD for the energy recovery wheel is programmed at the factory per the settings shown below for economizer and frost control modes. The VFD provided is a Yaskawa model J1000. Refer to the VFD instruction manual that ships with the unit when making adjustments.
| Parameter | Setting – J1000 | |||
Access Level | 2 |
| |||
VFD Auto Start | 1 |
| |||
|
|
|
| ||
Carrier Frequency | 2 |
| |||
|
|
| |||
Ref Upper Limit | 100% or 66%* | ||||
|
|
| |||
Ref Lower Limit | 5% | ||||
Motor Rated FLA | Motor FLA | ||||
Motor | Must be less than | ||||
FLA | |||||
|
| ||||
6 |
| ||||
(Terminal S2) |
| ||||
|
|
|
| ||
5 |
| ||||
(MA, MB, MC) |
| ||||
|
|
|
| ||
Economizer Signal Source | Setting | ||||
Honeywell |
| Carel | |||
|
| ||||
Module |
| Controller | |||
|
|
| |||
Analog Frequency Reference | 0 |
| 100 | ||
(Gain) |
| ||||
|
|
|
| ||
Analog Frequency Reference | 99 |
| 0 | ||
(Bias) |
| ||||
|
|
|
| ||
Elect Thermal Overload | 2 |
| |||
|
|
|
| ||
Frequency Detection Level | 20 | ||||
Access Level | 0 |
| |||
|
|
|
|
|
*36 inch wheel is 66% (40 Hz). All other wheels are 100% (60 Hz).
Model ERV Energy Recovery Unit 17