Start-Up

Start-Up

DANGER

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.

WARNING

Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.

Do not operate energy recovery ventilator without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc.

CAUTION

Do not run unit during construction phase. Damage to internal components may result and void warranty.

General Start-Up Information

Every installation requires a comprehensive start- up to ensure proper operation of the unit. As part of that process, the following checklist must be completed and information recorded. Starting up the unit in accordance with this checklist will not only ensure proper operation, but will also provide valuable information to personnel performing future maintenance. Should an issue arise which requires factory assistance, this completed document

will allow unit experts to provide quicker resolve. Qualified personnel should perform start-up to ensure safe and proper practices are followed.

Unit Model Number ________________________________

(e.g. ERV-361)

Unit Serial Number ________________________________

 

(e.g. 04C99999 or 10111000)

Energy Wheel Date Code___________________________

 

(e.g. 0450)

Start-Up Date

________________________________

Start-Up Personnel Name___________________________

Start-Up Company ________________________________

Phone Number

________________________________

Pre Start-Up Checklist – check as items are

completed.

oDisconnect and lock-out all power switches

oRemove any foreign objects that are located in the energy recovery unit.

oCheck all fasteners, set-screws, and locking collars on the fans, bearings, drives, motor bases and accessories for tightness.

22Model ERV Energy Recovery Unit

oRotate the fan wheels and energy recovery wheels by hand and ensure no parts are rubbing. If rubbing occurs, refer to Start-Up section for more information.

oCheck the fan belt drives for proper alignment and tension (refer to Start-Up section for more information).

oFilters can load up with dirt during building construction. Replace any dirty pleated filters and clean the aluminum mesh filters in the intake hood (refer to Routine Maintenance section).

oVerify that non-motorized dampers open and close properly.

oCheck the tightness of all factory wiring connections.

oVerify control wire gauge (refer to the Electrical Connections section).

oVerify diameter seal settings on the energy recovery wheel (refer to Start-Up section for more information).

SPECIAL TOOLS REQUIRED

Voltage Meter (with wire probes)

Amperage Meter

Thermometer

Tachometer

Incline manometer or equivalent

Start-Up Checklist

The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data must be collected while the unit is running. In order to measure volts & amps, the control center door must be open, and the unit energized using a crescent wrench to turn the disconnect handle.

Check line voltage at unit disconnect

________

L1-L2 volts

 

 

 

 

________

L2-L3 volts

 

 

 

 

________

L1-L3 volts

 

 

 

 

Motor Amp Draw

 

 

 

 

• Supply Fan

• Exhaust Fan

________

L1 amps

_______

L1 amps

________

L2 amps

_______

L2 amps

________

L3 amps

_______

L3 amps

• Energy Wheel

 

 

 

 

________

L1 amps

 

 

 

 

________

L2 amps

 

 

 

 

________

L3 amps

 

 

 

 

Fan RPM

 

 

 

 

 

________

Supply Fan

_______

Exhaust Fan

Correct fan rotation direction

 

 

 

Supply Fan

Yes

/

No

Exhaust Fan

Yes

/

No