Greenheck Fan FSD-211 dimensions Application Data, Damper Sleeve Dimensional Data

Models: FSD-211

1 7
Download 7 pages 6.39 Kb
Page 6
Image 6
Application Data

Application Data

Damper Sleeve Dimensional Data

The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation of retaining angles and duct connections.

The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.

Damper Sleeve Dimensional Data 11/2 in. max.

 

 

 

33/4 in.

 

6 in.

Varies

 

 

 

 

53/8 in.

LH

RH

 

 

 

Right hand drive is shown

A

5 in.

 

Left hand drive available upon request

 

 

Actuators and Accessories Sleeve Length

in. (mm)

"A" Dimension

 

 

Standard

Maximum

 

 

 

 

All Dampers*

7 3/16 (183)

12 (305)

 

 

 

When H is 11 in. (279mm) or

12 (305)

12 (305)

less with OCI, RRL, or TOR

 

 

 

 

 

*With the exception of dampers 10 in. high (254mm) or less.

NOTE: Entire damper frame is not required to be installed within the wall. The damper blades, when closed should be contained within the wall.

Actuators and Accessories

Space Envelopes

 

 

 

T*

Externally mounted actuators always require space outside

 

 

 

 

 

of the damper sleeve. The “S” dimension illustrates the

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

clearance required for various available actuators.

 

 

 

 

 

 

On dampers less than 18 in. (457mm) high, actuators may also require clearances above and/or below the sleeve. “B” and “T” dimensions are worst case clearance requirements for some dampers less than 18 in. (457mm) high. All damper sizes under 18 in. (457mm) high do not require these worst case clearances. If space availability above or below the damper sleeve is limited, each damper size should be individually evaluated.

B*

 

B*

T*

 

Actuator Type/Model

 

 

S

With

With

 

RRL, RRL/OCI, or TOR

RRL, RRL/OCI, or TOR

 

 

 

 

 

 

120 Volt AC

 

 

 

 

 

ML-4XXX Series Honeywell

5¼ in. (133mm)

¾ in.(19mm)

6 in. (152mm)

 

 

 

 

MS-4XXX Series Honeywell

6 in. (152mm)

3/8 in. (10mm)

6 in. (152mm)

 

 

 

 

MS-4120 Series Honeywell

6 in. (152mm)

3/8 in. (10mm)

6 in. (152mm)

 

 

 

 

 

24 Volt AC

 

 

 

 

 

ML-8XXX Series Honeywell

5¼ in. (133mm)

¾ in.(19mm)

6 in. (152mm)

 

 

 

 

MS-8XXX Series Honeywell

6 in. (152mm)

6 in. (152mm)

6 in. (152mm)

 

 

 

 

MS-8120 Series Honeywell

6 in. (152mm)

6 in. (152mm)

6 in. (152mm)

 

 

 

 

 

Pneumatic (25 psi min.)

 

 

 

 

 

331-4551 Powers

1 in. (25mm)

6¼ in. (159mm)

6½ in. (165mm)

 

 

 

 

331-2976 Powers

2 3/8 in. (60mm)

12 1/8 in. (308mm)

9¼ in. (235mm)

 

 

 

 

MK2-7121 Invensys

3 3/4 in. (95mm)

16½ in. (419mm)

10 in. (254mm)

 

 

 

 

* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .