| Model | ||
APPLICATION | Combination FIRE SMOKE DAMPERS | ||||||||
Model |
|
|
|
|
| Steel | |||
blades. The |
|
|
|
|
| UL 555S Leakage Class I | |||
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire |
|
|
| UL555 11⁄2 Hour Fire Resistance Rating | |||||
smoke situations. Model |
|
|
| ||||||
|
|
|
|
|
| ||||
blades running horizontal) or horizontally and is rated for airflow and | Model | ||||||||
leakage in either direction. |
| ||||||||
| dampers, smoke dampers and combination fire | ||||||||
|
|
| |||||||
Ratings |
| smoke dampers established by: | |||||||
UL 555 Fire Resistance Rating | National Fire Protection Association | ||||||||
Fire Rating: | 11⁄2 Hours | NFPA Standards 80, 90A, 92A, 92B, 101 & 105 | |||||||
Dynamic Closure Rating: Actual ratings are size dependent | IBC | International Building Codes | |||||||
Maximum Velocity: | 2000 fpm (10.2 m/s) | ||||||||
ICBO Uniform Building Codes | |||||||||
Maximum Pressure: | 4 in. wg (1 kPa) | ||||||||
CSFM California State Fire Marshal | |||||||||
Maximum Temperature: 350ºF (177°C) | |||||||||
|
| actuator | Fire Damper Listing | ||||||
UL 555S Leakage Rating |
| Leakage (Smoke) Damper Listing | |||||||
| New York City (MEA listing | ||||||||
Leakage Class: | I | ||||||||
Operational Rating: | Actual ratings are actuator dependent |
|
|
|
|
|
| ||
Maximum Velocity: | 2000 fpm (10.2 m/s) |
|
|
|
|
|
| ||
Maximum Pressure: | 4 in. wg (1 kPa) | “UL CLASSIFIED (see complete marking on | |||||||
Maximum Temperature: 350ºF (177°C) - Depending on | |||||||||
|
| actuator | product)” | ||||||
|
|
| “UL CLASSIFIED to Canadian safety standards | ||||||
Standard Construction | (see complete marking on product)” | ||||||||
Frame: | 5 in. x 1 in. (127mm x 25mm) |
|
|
| Standard 555 & 555S (Listing #R13317) | ||||
|
| galvanized steel hat channel with |
|
|
|
|
|
| |
|
| reinforced corners. A low profile head |
|
|
| Greenheck Fan Corporation certifies that the | |||
|
| and sill are used on sizes less than |
|
|
| model | |||
|
| 17 in. (432mm) high to maximize free |
|
|
| the AMCA Seal. The ratings shown are based on | |||
|
| area and performance. |
|
|
| tests and procedures performed in accordance | |||
Blades: |
|
|
| with AMCA Publication 511 and comply with | |||||
16 ga. (1.5mm) galvanized steel, |
|
|
| ||||||
|
|
| the requirements of the AMCA Certified Ratings | ||||||
|
| reinforced with 3 longitudinal | R | ||||||
|
|
|
|
| Programs. The AMCA Certified Ratings Seal | ||||
|
| structurally designed vee’s. |
|
|
| ||||
Seals: |
|
|
| applies to air performance ratings only. | |||||
Extruded silicone rubber blade seals |
|
|
|
|
|
| |||
Jamb Seals: | Flexible stainless steel jamb seals |
|
|
|
|
|
| ||
Linkage: | Concealed in jamb. |
|
|
|
|
|
| ||
Closure Device: | UL listed 165°F (74°C) RRL |
|
|
|
|
|
| ||
Axles: | 1⁄2 in. (13mm) dia. plated steel |
|
|
|
|
|
| ||
Bearings: | Bronze sleeve type |
|
|
|
|
|
| ||
|
|
|
| W* |
| ||||
|
|
|
|
|
|
|
| ||
Size Limitations: |
|
|
|
|
|
|
| ||
Minimum Size: | 8 in. W x 6 in. H (203mm W x 152mm H) |
|
|
|
|
|
| ||
Maximum Size: | Single Section: 32 in. W x 50 in. H |
|
|
|
|
|
| ||
|
| (813mm W x 1270mm H) |
|
|
|
|
|
| |
|
| 36 in. W x 48 in. H |
|
|
|
|
|
| |
|
| (914mm x 1219mm) |
|
|
|
|
|
| |
|
| Multiple Section: |
|
|
|
|
| RH | |
|
| Horizontal: 144 in. W x 96 in. H |
|
|
|
|
|
| |
|
| (3658mm W x 2438mm H) |
|
|
|
|
|
| |
|
| Vertical: 128 in. W x 100 in. H |
|
|
|
|
|
| |
|
| (3251mm W x 2540mm H) |
|
|
|
|
|
| |
Optional Features: |
| H* |
|
|
| ||||
|
|
|
|
|
| ||||
• RRL/OCI (Open closed indication switches) |
|
|
|
|
|
| |||
• Electric or pneumatic actuators |
|
|
|
|
|
| |||
• POC retaining angles |
|
|
|
|
|
|
| ||
• Smoke detectors |
|
|
|
|
|
|
| ||
• Momentary switch |
|
|
|
| LH | ||||
|
|
|
| ||||||
• Pneumatic Relief Valve (PRV) |
|
|
|
| |||||
|
|
|
|
|
|
| |||
• Security bars |
| *W&H dimensions furnished approximately ¼in. (6mm) undersize. | |||||||
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure | |||||||||
(Add sleeve thickness for overall sleeved damper dimension) | |||||||||
allows damper to perform smoke management functions during a | |||||||||
Right hand drive is shown. Left hand drive is available upon request. | |||||||||
fire emergency) |
|
|
|
|
|
|
|
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C) RRL's available.
• Sealed transitions and sleeves