Combination FIRE SMOKE DAMPERS
Application
Model
Model
Ratings
UL 555 Fire Resistance Rating |
|
Fire Rating: | 11⁄2 Hours |
Dynamic Closure Rating: Actual ratings are size dependant | |
Maximum Velocity: | 10.2 m/s |
Maximum Pressure: | 1 kPa |
Model FSD-M211
Steel 3V Blades
UL 555S Leakage Class I
UL555 11⁄2 Hour Fire Resistance Rating
4 Hour Fire Resistance Rating (BS476)
Model
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
ICBO Uniform Building Codes
SBCCI Standard Building Codes
British Standard BS476
Tested to 4 hours at Warrington Fire, UK
UL 555S Leakage Rating |
|
Leakage Class: | I |
Operational Rating: Actual ratings are actuator dependant | |
Maximum Velocity: | 10.2 m/s |
Maximum Pressure: | 1 kPa |
Max. Temperature: | 177°C |
BS476 Fire Resistance Rating |
|
Fire Rating: | 4 hours |
Standard Construction
Frame: | 127mm x 25mm galv. steel hat |
| channel with reinforced corners . A |
| low profile head and sill are used on |
| sizes less than 432mm high to |
| maximize free area and |
| performance. |
Blades: | 1.5mm galvanized steel, reinforced |
| with 3 longitudinal structurally |
| designed vee’s. |
Seals: | Extruded silicone rubber blade |
| seals. Flexible stainless steel jamb |
| seals. |
Closure Device: | 74°C RRL |
Linkage: | Concealed in jamb. |
Axles: | 13mm diameter plated steel |
Bearings: | Bronze sleeve type. |
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
|
|
|
|
| Greenheck Kunshan Co. Ltd. and Greenheck Fan | |
|
|
|
|
| Corporation certifies that the model | |
|
|
|
|
| ||
|
|
|
|
| shown herein is licensed to bear the AMCA Seal. The | |
|
|
|
| AIR | ratings shown are based on tests and procedures | |
|
|
|
| performed in accordance with AMCA Publication | ||
|
|
| PERFORMANCE | |||
AIR | 511 and comply with the requirements of the AMCA | |||||
Certified Ratings Programs. The AMCA Certified | ||||||
MOVEMENT | ||||||
AND CONTROL | Ratings Seal applies to air performance ratings only. | |||||
ASSOCIATION | ||||||
INTERNATIONAL, INC.® |
|
W
Size Limitations
Minimum Size: | 101mm W x 101mm H |
Maximum Size: |
|
Single Section: | 813mm W x 1270mm H |
| or 914mm W x 914mm H |
Multiple Section: | 3251mm W x 2540mm H Vertical |
| or 3658mm W x 2438mm H |
| Horizontal |
H
RH
Optional Features
•Stainless steel bearings
•100°C, and 177°C RRL available (UL only)
•69°C fusible link (BS476)
•Electric or pneumatic actuators to accomplish smoke management and system functions.
•Sleeve with Integral flange on both sides available
•RRL/OCI (open close indication)
•TOR (remote override of 74°C or 100°C closure allows damper to perform smoke management functions during a fire emergency)
LH
*W & H dimensions furnished approximately 6mm undersize. (Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com