![Part number 469419](/images/new-backgrounds/67535/675351x1.webp)
|
| Part number 469419 | ||
® |
| Firestop Material | ||
INSTALLATION INSTRUCTION SUPPLEMENT | ||||
Refer to: | DFD Series |
| ||
‘Installation Instructions for |
| |||
11/2 Hour | ||||
Smoke Dampers’ (Part #461336) | FSD Series |
| ||
|
| |||
These instructions apply to 11⁄2 hour rated combination | 11/2 Hour Combination Fire Smoke | |||
|
| |||
fire smoke dampers and dynamic rated |
| |||
|
|
| ||
fire dampers mounted in masonry, block, or metal or |
|
|
| |
wood stud walls. Note: This installation is intended | Recommended clearances, for width and/or height dimen- | |||
for underfloor applications where the damper/duct is | ||||
sions of: |
|
| ||
directly above (4 in. [101mm] or less) the rated concrete |
|
| ||
1) 48 in. (1219mm) or less: 3⁄4 in. (19mm) clearance | ||||
floor (see Figure 2). No duct impact test was conducted. | ||||
|
|
| ||
Specific requirements in these instructions are mandatory. | 2. Packing (optional) - Polyethylene backer rod, recessed from | |||
These instructions meet the requirements of UL 555. | ||||
surfaces of wall to accommodate the required thickness of | ||||
Installation shall comply with the requirements of NFPA | ||||
fill material. |
|
| ||
90A (Standard for the Installation of Air Conditioning and |
|
|
| |
Ventilating Systems) and UL Classification R13317. | 3. Fill Material - Hilti Corporation - | |||
Fire and Combination Fire/Smoke dampers up to a | applied to a minimum 5/8 in. (16mm) thickness within the | |||
annular space and flush with both surfaces of the wall | ||||
maximum size of 72 in. W x 96 in. H (1828mm x 2438mm) | ||||
with a 1 in. (25mm) overlap onto the gypsum board. If the | ||||
may be installed as instructed below. | ||||
damper/sleeve assembly comes into contact with the wall, | ||||
| ||||
1. Expansion Clearance - Fire damper and sleeve | a minimum of 3/8 in. (10mm) diameter bead shall be applied | |||
to the interface between the sleeve and contact surface. | ||||
assemblies expand during periods of intense heat. | ||||
Firestop should be installed according to manufacturers | ||||
Therefore, it is essential that openings in walls or | ||||
instructions and firestop instructions given in the 2007 UL | ||||
floors be larger than the fire or fire/smoke damper and | ||||
Fire Resistance Directory Volume 2B, page 4471. | ||||
sleeve assembly to allow for this expansion. Minimum | ||||
|
|
| ||
clearances required between the outside of fire or fire/ | 4. Retaining Clip - Retaining clip 1 in. x 2 in. x 2 in. x 16 gauge | |||
smoke damper sleeve assemblies and wall openings | ||||
(25mm x 51mm x 51mm x 1.5mm) is attached to one side of | ||||
are: | ||||
the wall with 1 1/2 in. (38mm) long #8 sheet metal screws or | ||||
• Galvanized steel fire dampers and sleeves: 1⁄8 in. | ||||
(3mm) per foot of damper width and height with a | masonry screws in the masonry wall. The 1 in. (25mm) leg of | |||
the clip shall be attached to the damper sleeve with 1/2 in. | ||||
minimum clearance of 1⁄4 in. (6mm), maximum of 1 | ||||
1⁄2 in. (38mm). Recommended clearances, for width | (13mm) long #10 sheet metal screws. The retaining clips are | |||
and/or height dimensions of: | required to be spaced a maximum of 6 in. (152mm) from the | |||
top of the sleeve and spaced a maximum of 12 in. (305mm) | ||||
1) 48 in. (1219mm) or less: 1⁄2 in. (13mm) | ||||
clearance | on center on the sides of the unit only. |
| ||
|
|
| ||
2) More than 48 in. (1219mm) and 96 in. |
|
|
| |
(2438mm) or less: 1 in. (25mm) clearance |
|
| Rated wall | |
3) More than 96 in.(2438mm): 11⁄2 in. (38mm) | Floor tiles |
| ||
clearance |
|
|
| |
• Stainless steel fire/smoke dampers and stainless |
|
|
| |
steel or galvanized sleeves: 3⁄16 in. (4.7mm) per |
|
| Fill material | |
|
|
| ||
foot of damper width and height with a minimum |
|
|
| |
clearance of 1/4 in. (6mm) , maximum of 2 in. |
| Retaining |
| |
(51mm) | Ductwork |
| ||
clip |
| |||
|
|
| ||
| max. 4 in. (102mm) | Fill material | ||
| (one side only on bottom) | |||
|
|
| ||
| Rated masonry floor |
|
| |
Figure 1 |
|
| Figure 2 |
Copyright © 2008 Greenheck Fan Corporation Firestop Material IOM Rev 2 Mar 2008