Greenheck Fan DFD Series installation instructions Part number, Firestop Material, FSD Series

Models: DFD Series FSD Series

1 1
Download 1 pages 56.7 Kb
Page 1
Image 1
Part number 469419

 

 

Part number 469419

®

 

Firestop Material

INSTALLATION INSTRUCTION SUPPLEMENT

Refer to:

DFD Series

 

Installation Instructions for FSD-XXX,DFD-XXX,

 

SSFSD-XXX & CFSD-XXX Series Fire & Combination Fire

11/2 Hour Multi-Blade Fire Dampers and

Smoke Dampers’ (Part #461336)

FSD Series

 

 

 

These instructions apply to 11⁄2 hour rated combination

11/2 Hour Combination Fire Smoke

Dampers-Vertical Mount

 

fire smoke dampers and dynamic rated multi-blade

 

 

 

 

fire dampers mounted in masonry, block, or metal or

 

 

 

wood stud walls. Note: This installation is intended

Recommended clearances, for width and/or height dimen-

for underfloor applications where the damper/duct is

sions of:

 

 

directly above (4 in. [101mm] or less) the rated concrete

 

 

1) 48 in. (1219mm) or less: 34 in. (19mm) clearance

floor (see Figure 2). No duct impact test was conducted.

 

 

 

Specific requirements in these instructions are mandatory.

2. Packing (optional) - Polyethylene backer rod, recessed from

These instructions meet the requirements of UL 555.

surfaces of wall to accommodate the required thickness of

Installation shall comply with the requirements of NFPA

fill material.

 

 

90A (Standard for the Installation of Air Conditioning and

 

 

 

Ventilating Systems) and UL Classification R13317.

3. Fill Material - Hilti Corporation - FS-One fire stop caulk

Fire and Combination Fire/Smoke dampers up to a

applied to a minimum 5/8 in. (16mm) thickness within the

annular space and flush with both surfaces of the wall

maximum size of 72 in. W x 96 in. H (1828mm x 2438mm)

with a 1 in. (25mm) overlap onto the gypsum board. If the

may be installed as instructed below.

damper/sleeve assembly comes into contact with the wall,

 

1. Expansion Clearance - Fire damper and sleeve

a minimum of 3/8 in. (10mm) diameter bead shall be applied

to the interface between the sleeve and contact surface.

assemblies expand during periods of intense heat.

Firestop should be installed according to manufacturers

Therefore, it is essential that openings in walls or

instructions and firestop instructions given in the 2007 UL

floors be larger than the fire or fire/smoke damper and

Fire Resistance Directory Volume 2B, page 4471.

sleeve assembly to allow for this expansion. Minimum

 

 

 

clearances required between the outside of fire or fire/

4. Retaining Clip - Retaining clip 1 in. x 2 in. x 2 in. x 16 gauge

smoke damper sleeve assemblies and wall openings

(25mm x 51mm x 51mm x 1.5mm) is attached to one side of

are:

the wall with 1 1/2 in. (38mm) long #8 sheet metal screws or

• Galvanized steel fire dampers and sleeves: 18 in.

(3mm) per foot of damper width and height with a

masonry screws in the masonry wall. The 1 in. (25mm) leg of

the clip shall be attached to the damper sleeve with 1/2 in.

minimum clearance of 14 in. (6mm), maximum of 1

12 in. (38mm). Recommended clearances, for width

(13mm) long #10 sheet metal screws. The retaining clips are

and/or height dimensions of:

required to be spaced a maximum of 6 in. (152mm) from the

top of the sleeve and spaced a maximum of 12 in. (305mm)

1) 48 in. (1219mm) or less: 12 in. (13mm)

clearance

on center on the sides of the unit only.

 

 

 

 

2) More than 48 in. (1219mm) and 96 in.

 

 

 

(2438mm) or less: 1 in. (25mm) clearance

 

 

Rated wall

3) More than 96 in.(2438mm): 112 in. (38mm)

Floor tiles

 

clearance

 

 

 

• Stainless steel fire/smoke dampers and stainless

 

 

 

steel or galvanized sleeves: 316 in. (4.7mm) per

 

 

Fill material

 

 

 

foot of damper width and height with a minimum

 

 

 

clearance of 1/4 in. (6mm) , maximum of 2 in.

 

Retaining

 

(51mm)

Ductwork

 

clip

 

 

 

 

 

max. 4 in. (102mm)

Fill material

 

(one side only on bottom)

 

 

 

 

Rated masonry floor

 

 

Figure 1

 

 

Figure 2

Copyright © 2008 Greenheck Fan Corporation Firestop Material IOM Rev 2 Mar 2008