Enthalpy Sensor
(Primary Sensor)
Timed Exhaust
Frost Control

ECONOMIZER APPLICATION/OPERATION

The energy recovery wheel may be de-energized for the purpose of providing economizer (free cooling) operation. This can be achieved with a signal from a Temperature or Enthalpy sensor mounted in the supply air inlet compartment (see FIGURE 13). This Primary sensor will de-energize the energy wheel when the outdoor air temperature (factory default is 65°F) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable set point. An additional Override temperature sensor is also furnished in the supply air inlet compartment to deactivate economizer mode (see FIGURE 13). The Override (with field adjustable set point) is set at some temperature lower than the Primary sensor (factory default is 50°F). Effectively, the two sensors create a deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into the building unconditioned.

Testing (terminals referenced below are in the unit control center — see FIGURE 5, Item #7)

 

Temperature sensor with Override

 

• Turn both Temperature and Override

 

thermostats down as low as they go.

FIGURE 13

The wheel should be rotating.

 

• Turn the Temperature sensor up as

 

high as it goes, and keep the Override

 

sensor as low as it will go. The wheel

 

should stop rotating.

• Turn both sensors as high as they will go. The wheel should start rotating.

• Set the Temperature sensor to the desired temperature for economizer operation to begin. Set the Override sensor to the desired temperature for economizer operation to end (factory default is 65°F and 50°F, respectively).

Override

Probes

Enthalpy sensor with Override

A factory-installed 620 ohm resistor is connected across terminals SR and +. The Override sensor should be turned

down below current temperature in unit. Turn the unit on; LED on the sensor should be off. Check continuity across 2 and 3, there should not be continuity. There should be continuity between terminals 1 and 2.

Disconnect the 620 ohm resistor from terminals SR and +. LED should turn on. There should be continuity between terminals 2 and 3. There should not be continuity between terminals 1 and 2.

Turn the Override sensor above current temperature in unit. There should be continuity between terminals 3 and 6. Set the Override sensor to the desired temperature for economizer operation to end (factory default is 50°F).

Reconnect the factory-installed jumper.

AUTO DRY CYCLE

The HRE may be supplied with a timer to delay turning off the unit to allow the evaporative cooler media pads to dry. The blowers continue to run for a user designated time (factory default is 1.5 hours) following a signal to turn the HRE unit off. The timer is located in the unit control center and can be adjusted from 15 minutes to 3 hours. This option is designed to prevent bacteria/mold growth on the pads. Refer to diagram in unit control center for wiring.

14

Page 14
Image 14
Greenheck Fan HRE-45, HRE-20, HRE-90, HRE-55 manual Economizer APPLICATION/OPERATION, Auto DRY Cycle

HRE-55, HRE-45, HRE-90, HRE-20 specifications

The Greenheck Fan HRE series, specifically the models HRE-20, HRE-90, HRE-55, and HRE-45, represents a blend of innovation and efficiency in the HVAC industry. Built for both commercial and industrial applications, these exhaust fans stand out due to their robust design and advanced operational features.

One of the main features of the HRE series is its energy-efficient motor design. These fans come equipped with a premium efficiency motor that reduces energy consumption while maintaining high performance. The motors are specifically designed to provide exceptional airflow while operating at lower sound levels, ensuring a quieter environment.

The HRE models also showcase advanced aerodynamic design, featuring optimized blade geometry that enhances airflow performance. This design ensures that the fans can deliver consistent and effective air movement even at varying operational conditions. This makes the HRE series suitable for use in a wide range of applications, from commercial kitchens to industrial processes.

Another significant characteristic of the HRE series is its durability. Constructed from high-quality materials, these fans are built to withstand harsh environmental conditions and prolonged usage. The robust casing and corrosion-resistant finishes ensure longevity, reducing the need for frequent repairs or replacements.

In terms of installation and maintenance, the HRE series offers significant advantages. The fans are designed for easy installation with clear mounting instructions. Additionally, maintenance procedures are simplified, allowing for hassle-free access to critical components, which reduces downtime and operating costs.

Technologically, the HRE models incorporate advanced controls and monitoring systems. These systems can offer real-time feedback on operational performance, allowing for proactive maintenance and energy management. Integrated controls can be customized to work with building management systems, providing users with seamless integration and control capabilities.

Overall, the Greenheck Fan HRE-20, HRE-90, HRE-55, and HRE-45 exemplify a commitment to quality and efficiency in commercial and industrial ventilation solutions. Their combination of energy efficiency, advanced design, durability, and user-friendly features make them a leading choice for those seeking reliable airflow solutions. These fans not only meet current industry standards but also set a benchmark for performance and innovation in the HVAC sector.