Greenheck Fan dimensions Model OFSD-312, Out of Wall Combination Fire Smoke Dampers, Ratings

Models: OFSD-312

1 6
Download 6 pages 43.39 Kb
Page 1
Image 1
Model OFSD-312

 

 

 

 

 

Model OFSD-312

Application

Out of Wall Combination Fire Smoke Dampers

Model OFSD-312 is an ‘out of the wall’ high performance combination

 

 

Steel Airfoil Blades

fire smoke damper with class II leakage. OFSD-312 is approved for

 

 

UL 555S Leakage Class I

use in walls, partitions, and floors with fire resistance ratings less than

 

 

UL555 112 Hour Fire Resistance Rating

3 hours. Removal of wall grille allows access to actuator and other

 

 

Horizontal or Vertical Mount

components. High strength airfoil blades insure the lowest resistance

 

 

 

 

to airflow in HVAC systems with velocities to 3000 fpm (15.2 m/s)

 

 

Model OFSD-312 meets the requirements for fire

and pressures to 4 in. wg (1 kPa). Model OFSD-312 shall be installed

dampers, smoke dampers and combination fire

 

vertically (with blades running horizontal) or horizontally and is rated

smoke dampers established by:

 

for airflow and leakage in either direction.

National Fire Protection Association

 

 

 

 

 

Ratings

 

 

NFPA Standards 80, 90A, 92A, 92B, 101 & 105

 

 

IBC

International Building Codes

 

UL555 Fire Resistance Rating:

 

ICBO Uniform Building Codes

 

Fire Rating:

112 hours in walls

 

CSFM California State Fire Marshal

 

Dynamic Closure Rating: Actual ratings are size dependent

 

 

Fire Damper Listing (#3225-0981:103)

 

Max. Velocity:

up to 3000 fpm (15.2 m/s)

 

 

 

Leakage (Smoke) Damper Listing (#3230-0981:104)

 

Max. Pressure:

4 in. wg (1 kPa) - differential pressure

 

 

UL555S Leakage Rating:

 

New York City (MEA listing #260-91-M)

 

Leakage Class:

I

 

 

 

 

Operational Rating:

Actual ratings are size dependent

 

 

 

 

 

 

 

 

Max. Velocity:

up to 3000 fpm (15.2m/s)

 

 

 

 

 

“UL CLASSIFIED (see complete marking on

 

Max. Pressure:

4 in. wg (1 kPa)

 

 

 

product)”

 

Max. Temperature:

350ºF (177ºC)- depending upon the

 

 

 

“UL CLASSIFIED to Canadian safety standards

 

 

 

actuator

 

 

 

 

 

(see complete marking on product)”

 

 

 

 

 

 

Standard Construction

 

 

Standard 555 & 555S (Listing #R13317)

 

Frame:

5 in. x 1 in. (127mm x 25mm)

 

 

 

 

 

 

galvanized steel hat channel with

 

 

Greenheck Fan Corporation certifies that the

 

 

reinforced corners. A low profile

 

 

 

 

 

 

model OFSD-312 shown herein is licensed to

 

 

head and sill are used on sizes less

 

 

bear the AMCA Seal. The ratings shown are

 

 

than 17 in. (432mm) high.

 

 

based on tests and procedures performed in

Blades:

Double skin airfoil shape of

 

 

accordance with AMCA Publication 511 and

 

 

comply with the requirements of the AMCA

 

 

galvanized steel with full length

 

 

 

 

 

 

Certified Ratings Programs. The AMCA Certified

 

 

structural reinforcement. 14 ga.

 

R

 

 

 

 

Ratings Seal applies to air performance ratings

 

 

(2mm) equivalent thickness.

 

 

only.

Seals:

Extruded silicone rubber blade seals.

 

 

 

 

 

 

Flexible stainless steel jamb seals.

 

 

 

 

Linkage:

Concealed in jamb

 

 

 

 

Fusible Link:

RRL 165°F (74ºC)

 

 

 

 

Axles:

12 in. (13mm) dia. plated steel

 

 

 

 

Bearings:

Bronze sleeve type

 

 

 

 

Sleeve:

Galvanized; wrapped with thermal

 

 

 

 

 

 

blanket

 

 

 

 

Size Limitations:

12 in.W x 12 in. H

 

 

 

 

Minimum Size:

 

 

 

 

Maximum Size:

(305mm x 305mm)

 

 

 

 

 

 

 

 

 

Single section:

32 in. W x 30 in. H

 

 

 

 

 

 

(813mm W x 762mm H)

 

 

 

 

Multiple Section:

36 in.W x 36 in. H

 

 

 

 

 

 

(914mm x 914mm)

 

 

 

 

Optional Features:

POC retaining Angles

RRL/OCI (open closed indication switches)

165ºF (74ºC), 212ºF (100ºC), 250ºF (121ºC), 350ºF (177ºC) RRL’s available

TOR (remote override allows damper to perform smoke

management functions during fire emergency.)

* W & H dimensions furnished approximately 14 in. (6mm) undersize.

• Electric or pneumatic actuators to accomplish smoke

Add blanket thickness (18 in.[3mm]) and sleeve thickness for

overall sleeved damper dimension)

management and system functions.

Oversize wall opening as follows:

• Smoke detectors

Nominal damper size plus 38 in.(9.5mm) (see Page 6)

• Momentary switch

 

• PRV (pneumatic relief valve)

 

• Security bars

Installation instructions available at www.greenheck.com

•Sealed transition and sleeves

 

Page 1
Image 1
Greenheck Fan dimensions Model OFSD-312, Out of Wall Combination Fire Smoke Dampers, Application, Ratings