Greenheck Fan PN 471755 manual Pre-Installation Checks, Wall Opening Requirements

Models: PN 471755

1 8
Download 8 pages 42.62 Kb
Page 3
Image 3
Pre-Installation Checks

Pre-Installation Checks

Check chart below for correct wall opening dimensions.

Check motor voltage and amperage rating for compatibility with electrical supply. Supply wiring must be properly fused and conform to local and national codes.

Motor load amperage must be checked and compared to nameplate rating to avoid serious damage to motor when speed is increased.

Wall Opening Requirements

Wall opening size and propeller-to-damper distance are two important dimensions for fan installation.

Fans mounted to the wall require a different wall opening (W.O.) size than those mounted in collars or wall housings. Propeller-to-damper distance (M) is important to reduce turbulence and damper flutter which may lead to premature damper failure.

Figure 1 and 2 show the wall opening (W.O.) required for installations with either a wall housing or collar.

Figure 3 shows the recommended wall opening (W.O.) and the minimum distance (M) suggested between the fan and damper for direct to wall installations.

Figure 4 shows the dimensions and wall opening (W.O.) required for installations with a filtered supply wall housing.

W.O.

W.O.

Figure 1 - Wall Housing Installation

Figure 2 - Wall Collar Installation

W.O.

Wall Housing

A

Filter

 

Wall

 

 

 

 

 

 

Section

INTERIOR

 

EXTERIOR

Optional 90º

 

 

 

 

 

 

 

 

 

 

Weatherhood

 

Filters

 

 

 

 

Filters

 

Airflow

 

 

 

 

 

Wall Opening Requirements M Manual background

Figure 3 - Direct to Wall Installation

C

24 in.

15 in.

Wall

Optional

 

B

 

Damper

 

 

 

 

 

 

 

Figure 4 - Filtered Supply Wall Housing Installation

 

Damper

Recommended Wall Opening (W.O.)

 

 

Filtered Supply Wall Housing Only

Fan

 

Square

 

M

 

 

 

 

 

 

 

 

Size

Size

 

 

 

Minimum

 

 

 

 

 

Figures 1

 

 

 

 

 

 

 

Square

Figure 3

Figure 4

A

B

C

 

Filter Quantity & Size

 

 

and 2

 

 

 

 

 

 

 

 

8

10 (254)

141/4 (362)

101 (267)

-

6 (152)

-

-

-

 

-

10

12 (305)

161/4 (413)

121 (318)

-

6 (152)

-

-

-

 

-

12

14 (356)

191/4 (489)

141 (368)

-

7 (178)

-

-

-

 

-

14

16 (406)

211/4 (540)

161 (419)

-

8 (203)

-

-

-

 

-

16

18 (457)

231/4 (591)

181 (470)

-

9 (229)

-

-

-

 

-

18

20 (508)

251/4 (641)

201 (521)

-

10 (254)

-

-

-

 

-

20

22 (559)

271/4 (692)

221 (572)

-

12 (305)

-

-

-

 

-

24

26 (660)

333/4 (857)

261 (673)

3334 (857)

13 (330)

3214 (819)

63 (1600)

24 (610)

4

2314 x 1614 (591 x 413)

30

32 (813)

393/4 (1010)

321 (826)

3934 (1010)

13 (330)

3814 (972)

65 (1651)

26 (660)

4

2458 x 1914 (625 x 489)

36

38 (965)

453/4 (1162)

381 (978)

4534 (1162)

14 (356)

4414 (1124)

6714 (1708)

281/4 (718)

6

2314 x 2218 (591 x 562)

42

44 (1118)

513/4 (1314)

441 (1130)

5134 (1314)

15 (381)

5018 (1273)

7278 (1851)

34 (864)

6

2418 x 2518 (613 x 638)

48

50 (1270)

573/4 (1467)

501 (1283)

5734 (1467)

16 (406)

5618 (1426)

7278 (1851)

34 (864)

12

2314 x 1834 (591 x 476)

54

56 (1422)

633/4 (1619)

561 (1435)

6334 (1619)

17 (432)

6238 (1584)

791116 (2024)

401116 (1033)

12

2314 x 2034 (591 x 527)

60

62 (1575)

693/4 (1772)

621 (1588)

-

19 (483)

-

-

-

 

-

72

74 (1880)

843/4 (2153)

741 (1892)

-

19 (483)

-

-

-

 

-

All dimensions given in inches (millimeters). Filters are 2 inch (51 mm) nominal thickness. Above filter sizes are actual dimensions.

Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply 3

®

Page 3