| Troubleshooting | ||
|
|
| |
WARNING: Before taking any corrective action, make certain unit is not capable of operation during repairs. | |||
|
|
| |
PROBLEM | CAUSE | CORRECTIVE ACTION | |
|
|
| |
Too Much Airflow | Resistance lower than designed | Decrease fan speed. | |
|
|
| |
|
| Check backdraft dampers for proper operation. Remove | |
| System resistance too high | obstructions in ductwork. Clean dirty filters. Check for adequate | |
|
| supply air for exhaust fans or exhaust air for supply fans. | |
Reduced Airflow | Fan too close to damper | Increase distance between fan and damper. | |
|
| ||
Fan speed too low | Increase fan speed. | ||
| |||
|
|
| |
| Excessive dirt buildup on | Clean propeller. | |
| propeller | ||
|
| ||
|
|
| |
| Bearings | Tighten collars and fasteners. Lubricate bearings. Replace | |
| defective bearings. | ||
|
| ||
|
|
| |
| Tighten pulleys on motor and fan shaft. Adjust belt tension. Align | ||
| pulleys properly. Replace worn belts or pulleys. See Maintenance. | ||
|
| ||
|
|
| |
|
| Clean dirt buildup from propeller. Check all setscrews and | |
Excessive Noise | Excessive vibration | fasteners for tightness. Check for worn bearing. Correct propeller | |
| imbalance. Check for loose dampers, guards or ductwork. | ||
|
| ||
| Defective motor | Replace motor. | |
|
|
| |
|
| Check VFD for drive setting, some controllers are able to be adjust | |
| Variable Frequency Drive (VFD) | to lower the harmonic noises sometimes heard during operation by | |
|
| adjusting a simple setting on the controller. | |
| Debris | Remove all debris from the fan. | |
|
|
| |
| Electrical Supply | Check fuses/circuit breakers. Check for switches turned off or | |
| disconnected. Check for correct supply voltage. | ||
|
| ||
Fan Does Not |
|
| |
Drive | Check for broken or worn belts. Tighten loose pulleys. | ||
Operate | |||
|
| ||
Motor | Assure motor is correct horsepower and not tripping overload | ||
| |||
| protector. | ||
|
| ||
|
|
|
Maintenance Documentation
Job Information
Job Name:___________________________________ | Service Organization:__________________________________ |
Address:_____________________________________ | Address:_____________________________________________ |
City:_________________________________________ | City:_________________________________________________ |
State:________________ Zip:__________________ | State:________________ Zip:___________________________ |
Phone:_______________________________________ | Phone:_______________________________________________ |
Contact Person:______________________________ | Work Done By:________________________________________ |
Nameplate Information | Field |
| ||
Model:_______________________________________ |
|
| ||
Volts:_ ________ Hertz:_________ Phase:_______ | Actual Voltage:________ Hertz:_______ | Phase:_________ | ||
Amps:_______________ | Mark:_________________ | Actual Amperage:_____________________________________ | ||
Supply hp:___________ | Exhaust hp:___________ | Blower Rotation:______________________________________ | ||
Serial Number:________________________________ | Air Volume: Design cfm:______________________________ | |||
Model Voltage:________________________________ | Actual cfm:______________________________ | |||
Motor Amperage:_ ____________________________ | Level of fan (L or H):___________________________________ | |||
Fan RPM:_ ___________________________________ | Fan RPM Range (min.)____________ (max.)______________ | |||
| Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply |
| ||
6 | ® |