Troubleshooting

 

Troubleshooting

 

 

 

WARNING: Before taking any corrective action, make certain unit is not capable of operation during repairs.

 

 

 

PROBLEM

CAUSE

CORRECTIVE ACTION

 

 

 

Too Much Airflow

Resistance lower than designed

Decrease fan speed.

 

 

 

 

 

Check backdraft dampers for proper operation. Remove

 

System resistance too high

obstructions in ductwork. Clean dirty filters. Check for adequate

 

 

supply air for exhaust fans or exhaust air for supply fans.

Reduced Airflow

Fan too close to damper

Increase distance between fan and damper.

 

 

Fan speed too low

Increase fan speed.

 

 

 

 

 

Excessive dirt buildup on

Clean propeller.

 

propeller

 

 

 

 

 

 

Bearings

Tighten collars and fasteners. Lubricate bearings. Replace

 

defective bearings.

 

 

 

 

 

 

V-Belt drive

Tighten pulleys on motor and fan shaft. Adjust belt tension. Align

 

pulleys properly. Replace worn belts or pulleys. See Maintenance.

 

 

 

 

 

 

 

Clean dirt buildup from propeller. Check all setscrews and

Excessive Noise

Excessive vibration

fasteners for tightness. Check for worn bearing. Correct propeller

 

imbalance. Check for loose dampers, guards or ductwork.

 

 

 

Defective motor

Replace motor.

 

 

 

 

 

Check VFD for drive setting, some controllers are able to be adjust

 

Variable Frequency Drive (VFD)

to lower the harmonic noises sometimes heard during operation by

 

 

adjusting a simple setting on the controller.

 

Debris

Remove all debris from the fan.

 

 

 

 

Electrical Supply

Check fuses/circuit breakers. Check for switches turned off or

 

disconnected. Check for correct supply voltage.

 

 

Fan Does Not

 

 

Drive

Check for broken or worn belts. Tighten loose pulleys.

Operate

 

 

Motor

Assure motor is correct horsepower and not tripping overload

 

 

protector.

 

 

 

 

 

Maintenance Documentation

Job Information

Job Name:___________________________________

Service Organization:__________________________________

Address:_____________________________________

Address:_____________________________________________

City:_________________________________________

City:_________________________________________________

State:________________ Zip:__________________

State:________________ Zip:___________________________

Phone:_______________________________________

Phone:_______________________________________________

Contact Person:______________________________

Work Done By:________________________________________

Nameplate Information

Field Start-Up Documentation

 

Model:_______________________________________

 

 

Volts:_ ________ Hertz:_________ Phase:_______

Actual Voltage:________ Hertz:_______

Phase:_________

Amps:_______________

Mark:_________________

Actual Amperage:_____________________________________

Supply hp:___________

Exhaust hp:___________

Blower Rotation:______________________________________

Serial Number:________________________________

Air Volume: Design cfm:______________________________

Model Voltage:________________________________

Actual cfm:______________________________

Motor Amperage:_ ____________________________

Level of fan (L or H):___________________________________

Fan RPM:_ ___________________________________

Fan RPM Range (min.)____________ (max.)______________

 

Sidewall Propeller Fans • Exhaust, Supply and Filtered Supply

 

6

®

Page 6
Image 6
Greenheck Fan PN 471755 manual Troubleshooting, Maintenance Documentation, Job Information, Nameplate Information