Greenheck Fan 464603 Size Limitations, Manually operated dampers IMO-310 & SSIMO-310, RRL Wiring

Models: 464603 IMO-XXX Series IMO-XXX SSIMO-XXX Series

1 4
Download 4 pages 56.25 Kb
Page 3
Image 3
Size Limitations

Size Limitations

 

Damper model

Maximum Single

Maximum Overall size for

 

 

 

Section size

Multi-section dampers

 

 

IMO-310

32 in. x 32 in.

64 in. x 32 in.

 

 

 

(813mm x 813mm)

(1626mm x 813mm)

 

 

 

SSIMO-310

32 in. x 32 in.

64 in. x 32 in.

 

 

 

(813mm x 813mm)

(1626mm x 813mm)

 

 

IMO-311

32 in. x 32 in.

64 in. x 32 in.

 

 

 

(813mm x 813mm)

(1626mm x 813mm)

 

 

SSIMO-311

32 in. x 32 in.

64 in. x 32 in.

 

 

 

 

(813mm x 813mm)

(1626mm x 813mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Manually operated dampers (IMO-310 & SSIMO-310)

Manually operated dampers utilize a spring and fusible link assembly to close the damper during elevated temperature conditions. No electrical power is required for these models.

Motor operated dampers (IMO-311 & SSIMO-311)

Motor operated dampers are supplied with an electric thermal response device which cuts power to the spring return actuator upon sensing an elevated temperatures. See below for electrical connections.

Connection and Operation of Temperature Response Devices (RRL standard, OCI option, and PRV option)

RRL - Dampers will be supplied with a thermostat-type temperature response device, as a standard. The device is a RRL (resettable link device), which only incorporates one thermostat and therefore the damper remains closed as soon as its sensor temperature is reached. The RRL does not contain blade indication switches. Refer to Figure 5 for wiring of the RRL

thermostat.

If RRL is ordered with a pneumatic actuator, an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator.

OCI - The OCI (open or closed indicator) option contains a single pole, double throw switch used to indicate the damper blade position. The switch provides a positive open or closed signal when used in conjunction with remote indicator lights. Refer to Fig. 7 for wiring of the OCI option.

ELECTRICAL CAPACITY = 10 AMP @ 120 / 240 VAC

L1

 

 

RRL Wiring

L2

ORANGE

NC

BLACK

BLACK

M WHITE/RED

 

 

 

P

 

 

 

 

 

PRIMARY TEMP

ELECTRIC DAMPER

 

 

SENSOR

 

ACTUATOR OR PNEUMATIC

Fig. 5

 

 

 

SOLENOID VALVE

 

 

 

 

 

NOTE: THE SWITCH WIRES WRAPPED WITH

 

A BLUE MARKER INDICATE THE

 

 

CLOSED POSITION OF THE DAMPER.

ELECTRICAL CAPACITY = 10AMP @ 120 / 240VAC

L1

 

 

 

 

L2

 

 

 

OCI Wiring

 

 

 

 

 

 

BY OTHERS

YELLOW S1

YELLOW

 

 

 

 

NO

 

 

DAMPER

 

 

 

 

INDICATOR

YELLOW

 

S2

YELLOW

 

 

 

LIGHTS

 

 

 

NO

PRV - The PRV (pneumatic relief valve) option is heat responsive

 

Fig. 6

 

 

 

 

device used with pneumatic actuators. This can be used in place

 

 

 

of EP switch where a RRL is used. The PRV activates when

RATINGS

temperature in excess of the temperature of the fusible link are

 

 

 

 

detected. When the fusible link melts, air from the actuator is

Integral Switch Type: Single Pole, double throw

exhausted to close the dampers. Pneumatic actuators are to be

 

 

 

 

piped per local code.

 

Electrical Capacity: 10 Amps, 1/3 hp, 120 or 240 Vac

1/2 Amp, 125 Vdc; 1/4 Amp 250 Vdc 5 Amps, 120 Vac “L” (lamp load) 1.0 Amps, 24 Vac

1.5 Amps, 24 Vdc

Temperature Limit: 165° F (standard primary sensor) 212° F (optional primary sensor)

Page 3
Image 3
Greenheck Fan 464603 Size Limitations, Manually operated dampers IMO-310 & SSIMO-310, RRL Wiring, OCI Wiring, Ratings