Greenheck Fan SSIMO-XXX Series, 464603 warranty Installation Instructions, Insulating the Duct

Models: 464603 IMO-XXX Series IMO-XXX SSIMO-XXX Series

1 4
Download 4 pages 56.25 Kb
Page 2
Image 2
Installation Instructions

Installation Instructions

Greenheck’s IMO dampers were tested per the International Maritime Organization’s Fire Test Procedure (FTP) code in a Class A bulkhead and in a Class A deck for 60 minutes. The FTP code requires that the ductwork (coaming) be insulated and that the damper be bolted or welded to the duct.

1. Insulating the Duct

The ductwork must be insulated a minimum of 6 in. (152mm) on the damper side and 18 in. (457mm) on the non-damper side (see figures 1-4). Any US Coast Guard type approved insulation with an A60 rating can be used. The insulation is to be installed on the duct with 0.106 in. (2.7mm) steel pins and 1.12 in. x 1.24 in. x 0.4 in. (28mm x 31mm x 10mm) steel clips.

2. Attaching Damper to Duct

The damper can be installed to the duct using either bolts or welding. If bolts are used , they are to be a minimum of 0.375 in. (9.5mm) diameter and 1 in. (25mm) long. The fasteners should be spaced 6 in. (152mm) OC and a maximum of 2 in. (51mm) from the corners.

Horizontal Airflow- Vertical Damper mount

6 in. (152mm)

18 in. (457mm)

IF HEIGHT <=11.00 in. (279mm)

Fig. 1

6 in. (152mm)

18 in. (457mm)

IF HEIGHT >11.00 (279mm)

Fig. 2

Vertical Airflow- Horizontal Damper mount

18 in. (457mm)

6 in. (152mm)

6 in. (152mm)18 in. (457mm)

Fig. 3

Fig. 4

Page 2
Image 2
Greenheck Fan SSIMO-XXX Series, 464603 warranty Installation Instructions, Insulating the Duct, Attaching Damper to Duct