Performance Data
|
|
|
|
|
|
|
|
|
| Air Temperature Rise Through Unit (°F) |
|
|
|
|
|
|
|
|
|
| |||||||||||||
Model | Input | Output | 20 |
| 30 |
| 35 |
| 40 |
| 45 |
| 50 |
| 55 |
| 60 |
| 65 |
| 70 |
| 75 |
| 80 |
| 85 |
| 90 |
| 95 |
| 100 |
25 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||
Number | (MBH) | (MBH) |
|
|
|
|
|
|
|
|
|
|
|
| CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PVF 100 | 100 | 80 | 3704 | 2963 | 2469 | 2116 |
| 1852 |
| 1646 | 1481 |
| 1347 | 1235 | 1140 |
| 1058 |
| 988 |
| 926 | 871 | 823 | 780 |
| 741 | |||||||
PVF 150 | 150 | 120 | 5556 | 4444 | 3704 | 3175 |
| 2778 |
| 2469 | 2222 |
| 2020 | 1852 | 1709 |
| 1587 |
| 1481 |
| 1389 | 1307 | 1235 | 1170 |
| 1111 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PVF 200 | 200 | 160 | 7407 | 5926 | 4938 | 4233 |
| 3704 |
| 3292 | 2963 |
| 2694 | 2469 | 2279 |
| 2116 |
| 1975 |
| 1852 | 1743 | 1646 | 1559 |
| 1481 | |||||||
PVF 250 | 250 | 200 | 9259 | 7407 | 6173 | 5291 |
| 4630 |
| 4115 | 3704 |
| 3367 | 3086 | 2849 |
| 2646 |
| 2469 |
| 2315 | 2179 | 2058 | 1949 |
| 1852 | |||||||
PVF 300 | 300 | 240 | 11111 | 8889 | 7407 | 6349 |
| 5556 |
| 4938 | 4444 |
| 4040 | 3704 | 3419 |
| 3175 |
| 2963 |
| 2778 | 2614 | 2469 | 2339 |
| 2222 | |||||||
PVF 350 | 350 | 280 | 12963 | 10370 | 8642 | 7407 |
| 6481 |
| 5761 | 5185 |
| 4714 | 4321 | 3989 |
| 3704 |
| 3457 |
| 3241 | 3050 | 2881 | 2729 |
| 2593 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PVF 400 | 400 | 320 | 14815 | 11852 | 9877 | 8466 |
| 7407 |
| 6584 | 5926 |
| 5387 | 4938 | 4558 |
| 4233 |
| 3951 |
| 3704 | 3486 | 3292 | 3119 |
| 2963 |
Ratings shown are for elevations up to 2000 ft. For higher elevations, the input should be reduced by 4% per 1000 ft. of elevation above sea level. In Canada, from 2000 to 4500 ft in elevation, the unit must be derated to 90% of the input listed above. The unit shall also be used in accordance with standard CGA 2.17.
Furnace Controls
Staged Temperature Controls
For Energy Recovery Units without Temperature Control Package
The furnace stage controls are located in the furnace control center. One control is provided for each stage of heating. The discharge temperature setting is located on the control furthest to the left. The offset and differential settings for each stage are preset at the factory; however,
For Energy Recovery Units with Temperature Control Package
If
point may be adjusted on the controller (See Temperature Controller IOM).
Figure 3: Staged Controls
Staged Burner Adjustments
Setting Manifold Pressure for Two Stage Gas Control
1.Set the unit to high fire by setting the discharge temperature control or thermostat to its maximum setting. If the ambient temperature is warm, the unit may not stay at high fire.
2.Measure the burner manifold pressure at the manifold pressure test port (see Control Center Layout on page 3) using a “U” tube manometer. The pressure on high fire should be 3.5 in. wg for natural gas and 10 in. wg for LP gas. To change the pressure, adjust the regulator adjustment screw on the combination gas valve.
3.Set the unit to low fire by removing the wire from the high fire terminal on the combination gas valve.
4.The manifold pressure on low fire for natural gas should be 0.88 in. wg and 2.5 in. wg for LP gas. To change the pressure, use the low fire adjustment screw on the combination gas valve.
Solenoid
High Fire Adjustment
Low Fire Adjustment
High Fire
Terminal
Figure 4: Combination Gas Valve
5