Greenheck Fan SEFSDR-511 dimensions Specifications

Models: SEFSDR-511

1 2
Download 2 pages 63.27 Kb
Page 2
Image 2
Specifications

Retaining plate

 

 

CLEARANCE FOR

 

 

 

 

EXPANSION

 

 

DUCT

 

 

OPTIONAL BLADE POSITION

CONNECTION

 

 

INDICATOR AND/OR ELECTRIC

AREA

 

Do not place retainer

LINK.

 

 

 

 

 

 

plate in this groove

 

 

1.5 IN.

 

 

 

1.50 IN.

 

 

 

 

 

 

FUSIBLE LINK

 

 

 

 

(standard)

 

 

 

 

LOCATION

 

 

AIRFLOW

 

 

 

 

 

 

 

 

DUCT

 

 

 

 

CONNECTION

 

 

 

1.5 IN.

AREA

 

 

 

 

Optional

 

 

 

 

Second

 

 

 

 

Retaining

 

 

 

 

Plate

 

ACTUATOR

 

 

 

3.375 IN.

 

 

5.375 in.

3.06 in. or 7.43 in.*

 

 

 

 

 

6 IN. MAX

 

 

 

 

Wall Manual backgroundManual background 16.00 IN MAX

 

SLEEVE LENGTH

 

 

* 7.43 in. when OCI, RRL, RRL/OCI,

TOP VIEW OF DAMPER

 

 

TOR, or PRV is selected

Specifications

True round combination fire smoke dampers meeting the following specifications shall be furnished and installed where shown on plans and/or as described in schedules. Dampers shall meet the requirements of the latest edition of NFPA 80, 90A, 92, 92A, 101 & 105.

Damper shall be constructed of 20 ga. (1mm) 316 stainless steel frame; blades constructed of double skin 316 stainless steel round style blades; silicone rubber blade seals; ½

in. 316 stainless steel axles; 316 stainless steel bearings. Damper is provided with one retainer plate.

Dampers shall be tested, rated and labeled in accordance with the latest edition of UL standards 555 and 555S. Dampers shall have a UL 555 fire damper of 1 1/2 hours.

Each damper shall be equipped with a heat responsive device which has been tested and approved for use with the damper assembly in accordance with UL555. The heat responsive device shall have a temperature rating of (specifier select one of the following) 165º F (74ºC), 212º F (100ºC), 286º F (141ºC) , or 350º F (177ºC).

Damper actuators shall be factory mounted and qualified for use with the damper in accordance with UL555S. Damper actuators shall be (specifier select one of the following)

electric type for 120 (or 24) volt operation or pneumatic type for 25 psi minimum (30 psi maximum) operation. Manufacturer’s submittal data shall indicate actuator space requirements around the damper.

Dampers shall have a UL555S leakage rating of Class I and a temperature rating of 250ºF (121°C) minimum. Dampers shall have a UL555S operational airflow equal to or greater than the airflow at its installed location and an operational pressure rating of 4 in. wg (1 kPa).

All UL555 and UL555S dynamic closure ratings and leakage ratings shall be qualified for airflow and pressure in either direction through the damper. UL ratings shall allow for mounting damper vertically or horizontally.

The Damper manufacturer’s submittal data shall certify all air performance pressure drop data is tested in accordance with the AMCA certified ratings program for test figures 5.2, 5.3, and 5.5. Damper air performance shall be developed in accordance with the latest edition of AMCA standard 500-D.

Basis of design is Greenheck’s model SEFSDR-511.

Copyright © 2008 Greenheck Fan Corporation SEFSDR-511 Rev. 7 June 2008

Page 2
Image 2
Greenheck Fan SEFSDR-511 dimensions Specifications