| Combination Fire Smoke Dampers | ||||
|
| Round Stainless Steel Blade | ||||
Model |
| UL 555S Leakage Class I | ||||
| UL555 1 1/2 Hour Fire Resistance Rating | |||||
smoke damper with round style blade. The |
| |||||
qualified to 3000 fpm (15.2 m/s) and 4 in. wg (1 kPa) for operation |
|
|
| |||
| Model |
| ||||
and dynamic closure in emergency fire smoke situations. Model |
|
| ||||
| dampers, smoke dampers and combination fire smoke |
| ||||
|
| |||||
| dampers established by: |
| ||||
horizontal) or horizontally and is rated for airflow and leakage in |
|
| ||||
|
|
| ||||
either direction. |
|
| National Fire Protection Association |
| ||
|
|
|
|
| ||
Ratings |
|
| NFPA Standards 80, 90A, 92A, 92B 101 & 105 |
| ||
UL 555 Fire Resistance Rating |
| IBC International Building Codes |
| |||
| New York City (MEA listing |
| ||||
| Fire Rating: | 1 1/2 Hour |
|
| ||
|
| California State Fire Marshall |
| |||
Dynamic Closure Rating: Actual ratings are size dependant |
|
| ||||
| Listing #: |
| ||||
Maximum Velocity: | 3000 fpm (15.2 m/s) |
|
| |||
| Listing #: |
| ||||
Maximum Pressure: | 4 in. wg (1 kPa) |
|
| |||
UL 555S Leakage Rating |
|
| “UL CLASSIFIED (see complete marking on | |||
| Leakage Class: | I |
| |||
Operational Rating: | Actual ratings are actuator dependant |
| product)” | |||
Maximum Velocity: | 3000 fpm (15.2 m/s) |
| “UL CLASSIFIED to Canadian safety standards | |||
| (see complete marking on product)” | |||||
Maximum Pressure: | 4 in. wg (1 kPa) |
| ||||
| Standard 555 (Listing #R13317) | |||||
Maximum Temperature: | 350º F (177°C) | |||||
Standard 555S (Listing #R13447) | ||||||
|
|
|
|
Standard Construction
Frame/Sleeve: 20 ga. (1mm) 316 stainless steel integral sleeve
Blade: Double skin 316 stainless steel (14 ga. [2mm] equivalent) round style blade
Seal: Extruded silicone rubber blade seal
Axle: 1/2 in. (13mm) dia. 316 stainless steel Bearing: 316 stainless steel sleeve type
Fusible Link: UL listed 165ºF (74ºC)
Size Limitations
Minimum Size: 6 in. (152mm) diameter
Maximum Size: 24 in. (610mm) diameter
Optional Features
•OCI (Open closed indication switches)
•165ºF (74°C), 212ºF (100°C), and 350ºF (177°C) RRL - not 316SS.
•TOR (remote override of 165º F (74°C) closure allows damper to perform smoke management functions during a fire emergency)
•Electric or pneumatic actuators to accomplish smoke management and system functions.
•One retainer plate required, additional retainer plate available
•14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve
Opening + 2 in. Min.
D*
*Dimensions furnished approximately 1/8 in. (3mm) undersize.
Nut
Retaining
Plate Assembly
Minimum Wall/Floor Opening | Clamping |
| |
Screw |
| ||
= Nominal Dia. + 7/8 in. | Clamping Screw | ||
|
1.00 in. Min. Typ.
Fasteners
Installation instructions available at www.greenheck.com.