Greenheck Fan FDR-XXX Pre-Installation Guidelines, Clearances Required Between Fire, Openings

Models: DFDR-XXX FDR-XXX SSFDR-XXX SSDFDR-XXX

1 4
Download 4 pages 38.84 Kb
Page 2
Image 2
Table of Contents

Table of Contents

 

Pre-Installation Guidelines

2

Installation

2-4

Maintenance

4

Troubleshooting

4

Pre-Installation Guidelines

The basic intent of a proper installation is to secure the fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.

1)Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. Dampers will be supplied with a temperature responsive fusible link device. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place.

2)Lift or handle damper using the frame. Do not lift damper using blades.

3)Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper blade from opening and/or closing.

4)Damper must be installed into duct or opening free of distortion or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause torque requirements to exceed damper design.

5)Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: 1) Mortar dust 2) Drywall dust 3) Firesafing materials 4) Wall texture and 5) Paint overspray.

6)Damper should be sufficiently covered to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design.

7)Caulking is not allowed between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining plates and a field-applied sealant may be required for the damper sleeve and transitions to meet certain duct leakage standards.

8)ACCESS: Suitable access (such that fusible links can be maintained) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).

9)The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.

Installation - Failure to follow these instructions will void all warranties.

These instructions apply to 11/2 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555. The installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications R13317.

1. CLEARANCES REQUIRED BETWEEN FIRE

DAMPER SLEEVES AND WALL/FLOOR

OPENINGS

Fire damper assemblies expand during periods of

intense heat. Therefore, it is essential that openings in

walls or floors be larger than the fire damper assembly

to allow for this expansion. The wall/floor opening

must be a minimum of 7/8 in.(22mm) larger than the

outside diameter of the damper. Refer to Section 4 for

RETAINER PLATE (OPTIONAL)

DUCT CONNECTION

2 in.

AREA

 

 

 

AIRFLOW

CLEARANCE FOR EXPANSION

RETAINER PLATE BLADE LATCH

ACCESS DOOR TO BE ON SAME SIDE AS BLADE LATCH

 

DUCT CONNECTION

2 in.

AREA

 

additional installation considerations.

 

DO NOT PLACE RETAINER

 

PLATE IN THIS GROOVE

6 in. max.

6 in. max.

 

TW

 

SLEEVE LENGTH

2

Fig. 1

Page 2
Image 2
Greenheck Fan FDR-XXX warranty Pre-Installation Guidelines, Clearances Required Between Fire, Damper Sleeves And Wall/Floor