Image 4
6. Round Duct Connections

6. Round Duct Connections

Round duct connections shall be attached with #8 sheet metal screws as follows:

Ducts 22 in. (559mm) dia. and smaller shall have three screws.

Ducts larger than 22 in. (559mm) dia. and up to including 24 in. dia. shall have five screws.

NOTE: All breakaway connections described may have duct sealant, PA2084T Duct Sealant Adhesive manufactured by Precision or DP1010 Water Base Duct Sealant manufactured by Design Polymetrics, applied in accordance with SMACNA recommendations.

JO

JOPD

.BYJNVN

JOPD

JOPD

$FJMJOH3VOOFS

.BYJNVN

.BYJNVN

 

NFUBMTUVET

NFUBMTUVET

 

 

 

JO 

 

1BOIFBE

 

 

4DSFXT

JO 

 

 

JOPD

JOPD

 

.BYJNVN

.BYJNVN

 

XPPETUVET

XPPETUVET

 

DFDR-XXX Blade Orientation

Fig. 4

'MPPS3VOOFS

 

Axle

 

30°

 

 

 

Axle

 

 

30°

Axle

 

 

30° Off Horizontal

30° Off Horizontal

Normal

(Maximum)

(Maximum)

 

Damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.

Dampers must be maintained, cycled, and tested at intervals not less than every six months and in accordance with the latest editions of NFPA 90A & 92A, UL864 and local codes.

Damper Troubleshooting

The following is a possible cause and correction list for common concerns with the dampers.

Symptom

Possible Cause

Corrective Action

 

 

 

 

Frame is out of round causing blades to

Adjust frame such that it is round

Damper does not fully open and/or fully

interfere with frame

 

 

 

Screws interfere with blade

Locate screws and remove

close

 

 

Contaminants on damper

Clean with a non-oil based solvent (see

 

 

 

Damper Maintenance)

 

 

 

Link separated

Heat

Replace link

 

 

 

 