SSFSDR-512
Application
Model
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 Hour
Dynamic Closure Rating: Actual ratings are size dependant Maximum Velocity: 3000 fpm (15.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
UL 555S Leakage Rating
Leakage Class: II
Operational Rating: Actual ratings are actuator dependant
Maximum Velocity: 3000 fpm (15.2 m/s) Maximum Pressure: 4 in. wg (1 kPa)
Maximum Temperature: 350º F (177°C)
Standard Construction
Frame/Sleeve: 20 ga. (1mm) 304 stainless steel round integral sleeve
Blades: Double skin 304 stainless steel (14 ga. [2mm] equivalent) round style blades
Seals: Extruded silicone rubber blade seals Linkage: 304 stainless steel - concealed in jamb. Axles: 1/2 in. (13mm) dia. 304 stainless steel.
Bearings: 304 stainless steel sleeve type Fusible Link: UL listed 165ºF (74ºC)
Combination Fire Smoke Dampers
Round Stainless Steel Blade UL 555S Leakage Class II UL555 1 1/2 Hour Fire Resistance Rating
Model
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing
California State Fire Marshall
Listing #:
Listing #:
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 (Listing #R13317)
Standard 555S (Listing #R13447)
Size Limitations
Minimum Size: 6 in. (152mm) diameter
Maximum Size: 24 in. (610mm) diameter
Optional Features |
| |
• OCI (Open closed indication switches) |
| |
• 165º F (74°C), 212º F (100°C), and 350º F (177°C) RRL available |
| |
- not 304SS. |
| |
• TOR (remote override of 165º F (74°C) closure allows damper to |
| |
perform smoke management functions during a fire emergency) | D* | |
- not 304SS. | ||
|
• Electric or pneumatic actuators to accomplish smoke management | * Dimensions furnished approximately 1/8 in. (3mm) undersize. | |
and system functions. |
|
|
• One retainer plate required, additional retainer plate available. |
|
|
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve | Installation instructions available at www.greenheck.com. | |
| ||
Opening + 2 in. Min. |
| Nut |
Minimum Wall/Floor Opening | Clamping | Retaining | |
Screw | Plate Assembly | ||
= Nominal Dia. + 7/8 in. | |||
|
| ||
1.00 in. Min. Typ. |
| Clamping Screw | |
| Fasteners | ||
|
|