Model SSSMD-201 Smoke Dampers
Stainless Steel 3V Blade
UL 555S Leakage Class I
Application
Model
Ratings
Leakage Class: | l |
Pressure: | 4 in. wg (1 kPa) - differential |
| pressure |
Velocity: | Operational rated to 2000 fpm |
| (10.2 m/s) |
Temperature: | 350°F (177ºC) with all actuators. |
| Higher temperature ratings with |
| some actuators. |
Model
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555S (Listing #R13317)
Standard Construction
Frame: | 5 in. x 1 in. (127mm x 25mm) 16 ga. |
| (1.5mm) 304 stainless steel hat |
| channel with reinforced corners. A |
| low profile head and sill are used on |
| sizes less than 17 in. (432mm) high |
| to maximize free area and |
| performance. |
Blades: | 16 ga. (1.5mm) 304 stainless steel, |
| reinforced with 3 longitudinal |
| structurally designed vee’s. |
Seals: | Flexible 304 stainless steel jamb |
| seals. |
Linkage: | 304 stainless steel - concealed in |
Axles: | jamb. |
1/2 in. (13mm) dia. 304 stainless | |
| steel. |
Bearings: | 304 stainless steel sleeve type. |
Greenheck Fan Corporation certifies that the model
the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams. The AMCA Certified Ratings Seal applies to air performance ratings only.
W*
Size Limitations
Minimum Size: | 8 in. W x 6 in. H |
Maximum Size: | (203mm W x 152mm H) |
| |
Single Section - | 32 in. W x 50 in. H |
| (813mm W x 1270mm H) |
| 36 in. W x 48 in. H |
| (914mm W x 1219mm H) |
Multiple Section - | 144 in. W x 100 in. H |
| (3658mm W x 2438mm H) |
| 288 in. W x 50 in. H |
| (7315 mm W x 1270mm H) |
Optional Features
•OCI (Open closed indication switches)
•Electric or pneumatic actuators to accomplish smoke management and system functions.
•Fail open
RH
H*
LH
*W&H dimensions furnished approximately 1/4 in. (6mm) undersize. (Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com