Greenheck Fan USGF Typical Installation and Anchoring, Concrete Deck Anchoring, Corner Detail

Models: USGF

1 20
Download 20 pages 33.43 Kb
Page 8
Image 8
Typical Installation and Anchoring

Typical Installation and Anchoring

Typical Mounting - Fan to Curb

Fastener 4 in. (102 mm)

 

 

 

 

 

 

 

 

 

 

 

 

1/4 in. (6 mm) fastener minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from curb edge

 

 

H-GPF or SD curb

5/16 in. (8 mm) recommended

 

 

 

 

 

 

 

 

 

 

 

 

See table for fastener quantities

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

USGF

Fasteners

Total

Size

Per Side

Fasteners

 

 

 

140 - 160

5

20

 

 

 

180 - 200

5

20

 

 

 

Fasteners on each side of the fan are to be installed with one fastener 4 in. (102 mm) from each edge and one fastener centered. The remaining fasteners are to be equally spaced.

Concrete Deck Anchoring

Corner Detail

11/4 in. (32 mm)

11/4 in.

(32 mm)

 

 

 

 

 

 

 

Outside of Roof Curb

 

 

 

 

 

 

 

 

 

 

1 in. (25 mm) less than Fan Curb Cap

Use 3/8 in. (10 mm) expansion anchor

 

 

 

 

 

 

 

 

 

 

 

or equal into concrete.

 

 

 

 

 

 

 

 

 

 

 

Fasteners one on each corner as

 

 

 

 

 

 

 

 

 

 

 

detailed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 in. (25 mm) Insulation

Each side at center of unit. Maximum

 

 

 

 

 

 

H-GPF Curb Height

 

 

fastener spacing of 8 in. (203 mm),

 

 

 

 

 

 

 

add additional fasteners to satisfy.

8 to 18 in. (203 to 457 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Optional 24 in. (610 mm) SD Curb)

 

 

 

 

 

 

 

 

Roof Opening

 

Minimum Concrete

2-1/2 in. (64 mm)

Strength of 2000 PSI

Embedment Recommended

 

minimum 1-5/8 in. (41 mm)

Minimum 1-3/4 in. (44 mm)

 

edge distance

 

5 in. (127 mm) Mounting Flange

Center fasteners

 

on flange

Outside Flange

 

USGF

Fan Curb Cap

Roof Opening

Fasteners Per Side

Outside Flange

Size

 

 

 

 

 

 

 

 

 

141 - 161

22 x 22 (559 x 559)

181/2 x 181/2 (470 x 470)

5

31 x 31 (787 x 787)

 

 

 

 

 

180 - 200

30 x 30 (762 x 762)

201/2 x 201/2 (521 x 521)

7

39 x 39 (991 x 991)

 

 

 

 

 

All dimensions in inches (millimeters).