5.Connect the positive lead of the circuit to the return direction for “A” power on the OS-10 system termi- nal block. See wiring 2-A in Figure 7.

OnSite Series Getting Started Guide

3 • Installation Overview

 

 

The ground wire should always be connected first and discon- nected last.

CAUTION

5.Connect the positive lead of the circuit to the return direction for “A” power on the OS-10 system termi- nal block. See wiring 2-A in Figure 7.

Note The terminal block indicates the return direction for “A” power by the letter R. This lead is second from the top on the OS-10 system terminal block.

Note Step 4 and Step 5 results in the grounding of the return direction for “A” power on the OS-10 system terminal block.

6.Connect the negative lead of the circuit to the “A” power input lead on the OS-10 system terminal block. See wiring 3-A on figure 13 on page 36.

Note The terminal block indicates the “A” power lead by the letter A. This lead is first from the top on the OS-10 system terminal block.

Continue with the following steps if a second circuit is available for the provision of redundant “A” and “B” DC power inputs on the system. Otherwise, go directly to Step 10 to complete this task.

7.Connect the positive lead of this circuit to ground. See wiring 1-B on figure 13 on page 36.

Note As an option, you may choose another common grounding point other than the oneshown in Figure 13. The choice depends on the grounding practice for your particular location. Figure 13 shows the grounding point colocated with the DC circuit for “B” power.

The ground wire should always be connected first and discon- nected last.

CAUTION

8.Connect the positive lead of the circuit to the return direction for “B” power on the OS-10 Series system terminal block. See wiring 2-B on Figure 13.

Note The terminal block indicates the return direction for “B” power by the letter R. This lead is fourth from the top on the OS-10 system terminal block.

Note Step 7 and Step 8 result in the grounding of the return direction for “B” power on the OS-10 system terminal block.

OnSite System Installation

37

Page 37
Image 37
Patton electronic 1063, 07MOS10xx-GS manual