Patton electronic 07MOS10xx-GS Operating Environment Requirements, Distribution rack requirements

Models: 1063 07MOS10xx-GS

1 67
Download 67 pages 15.67 Kb
Page 26
Image 26
•Distribution rack requirements

OnSite Series Getting Started Guide

3 • Installation Overview

 

 

Distribution rack requirements

The following sections provide further details for each area.

Operating Environment Requirements

You need to verify that your site meets all environmental and safety requirements. During the early planning stages of installing or modifying your network, it is important that you develop a thorough understanding of the regulations that pertain to your location and industry.

Temperature – The OS-10 system generates a specified amount of heat as indicated on the data sheet. It is essential that you provide a temperature-controlled environment for both proper performance and safety.

Install the equipment only in a temperature- and humidity-controlled indoor area that is free of airborne mate- rials that can conduct electricity.

The following are some general thermal recommendations for your wiring closet or equipment room:

Ensure that the ventilation in the area is adequate to maintain a temperature below 50°C (122°F).

Install a reliable air conditioning and ventilation system.

Keep the ventilation in the wiring closet running during nonbusiness hours; otherwise, the equipment can overheat.

Maintain the following ambient operating temperature: 0° to 50° C (32° to 122°F)

Maintain the following storage temperature: –40° to 70°C (–40° to 158°F)

Airflow requirements – To ensure proper airflow through the OS-10 equipment, follow these recommenda- tions when you are installing your chassis:

Leave 7.62 cm (3 inches) of minimum clearance on both the left and right sides of the chassis.

Leave a half-rack unit (RU) of minimum clearance above and below the chassis for properairflow.

Note The OS-10 is a convection-cooled system, and adherence to these clearance requirements is required for proper operation of the system.

Humidity – Keep the operating humidity between 5 and 95 percent relative humidity (noncondensing).

Table 4 summarizes the acceptable operational conditions for the OS-10 system.

Table 4. Environmental Conditions for Operating the OS-10 System

 

Environment

Minimum

Maximum

 

 

 

 

 

Temperature

 

Ambient operating

5°C

+40°C

 

 

 

 

 

 

 

Short-term (96 hours)

0°C

+50°C

 

 

 

 

 

Humidity

 

Short-term (96 hours)

5%

80%

 

 

 

 

 

 

 

Short-term (96 hours)

5%

95%

 

 

 

 

 

Altitude

 

Ambient operating

–60 m

1800 m

 

 

 

 

 

Planning Your Site

26