GSW JWF307, JW727 JWF657, JW717, JW517, JW327 JWF507, JW317 Air Requirements, Air Supply, In Canada

Models: JW527 JWF307V JW727 JWF657 JWF307 JW327 JWF507 JW517 JW317 JW717

1 20
Download 20 pages 22.68 Kb
Page 6
Image 6
Air Requirements

VENT

 

 

 

 

 

 

 

 

 

DRAFT

RISE 20mm/m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REGULATOR

(1/4 in./ft.)

FILL CAP

 

SERVICE

 

BLOCKED VENT

 

 

 

 

 

 

 

SWITCH

 

SAFETY SWITCH

 

 

 

 

 

 

 

LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAUGE

T&P VALVE

 

 

 

 

OIL

AQUASTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATING

 

 

 

 

 

STORAGE

INSTRUCTIONS

 

TANK

CUT OFF VALVE

Air SupplyOIL FILTER

OIL

BURNER

Figure 4 INSTALLATION DIAGRAM

Air Requirements

An adequate supply of combustion and ventilation air is required to:

Ensure proper combustion.

Reduce risk of property damage, severe bodily injury or death from possible flue gas leakage and carbon monoxide emissions.

Do not install an exhaust fan in the same room as the water heater.

Satisfactory combustion cannot be sustained in an area that is not provided with fresh air. Fresh air contains oxygen that is necessary for proper combustion. If the water heater is installed in a confined space, sufficient fresh air must be drawn in from outside of the enclosure.

NOTE: Lack of adequate fresh air supply may cause a poor flame.

Air Supply

CAUTION

IF AN ALL-HOUSE VENTILATION FAN IS USED, A SEPARATE OUTSIDE AIR DUCT MUST BE USED AND DUCTED TO THE FURNACE ROOM AND/OR ROOM WHERE THE WATER HEATER IS LOCATED.

In Canada:

If the water heater is installed in a house built to the require- ments of the “National Building Code of Canada, 1985”, or a subsequent edition, the space shall be provided with a air inlets as outlined below, or have a mechanical air-supply system of sufficient equivalent capacity. If a mechanical air- supply system is used, it shall be interlocked to the appli- ance or equipment.

NOTE: In unconfined spaces in buildings of conventional frame, brick, or stone construction built prior to the require- ments of the “National Building Code of Canada, 1985”, and not subsequently significantly air-tightened, infiltration is normally adequate to provide air for combustion and some ventilation; however, there may be notable exceptions. Houses built in accordance with the “National Building Code of Canada, 1985” (or subsequent edition), with exten-

sive exterior stucco coating, or with a sealed vapour barrier or other similar air sealing technique, will often be sufficient- ly airtight so that there is not sufficient air for both combus- tion and venting the products of combustion of an oil-fired appliance, or for replacing the air vented by other exhaust devices within the house.

Outdoor Combustion & Ventilation Air (Unconfined space)

If the water heater is installed in an unconfined space in a building having insufficient infiltration, additional air for com- bustion and ventilation shall be obtained from outdoors or from spaces freely communicating with the outdoors. Under these conditions, permanent opening(s) shall be provided so that the total air received through these openings will be at least as much as would be admitted by openings having a total free area of 4.5 cm2/kWh (1 in2/5000 Btu/h) of the total input rating of all oil-fired appliances.

Outdoor Combustion & Ventilation Air (Confined space)

A heater installed in a confined space that obtains all of its air for combustion and ventilation from outside the building shall be provided with two permanent openings, one near the top of the enclosure and another near the bottom. Each opening shall communicate directly or by means of ducts with the outdoors or to such spaces (such as a crawl space) that freely communicate with the outdoors, and shall be sized in accordance with “Air Duct Sizing”.

Outdoor Combustion Air & Indoor Ventilation Air (Confined space)

An appliance located in a confined space that obtains its combustion air from outdoors and ventilation air from within the conditioned space of the building shall be provided with two permanent openings for ventilation. One located near the top of the enclosure and another near the bottom. Each opening shall have a free area of not less than 19.5 cm2/kWh (1 in2/1000 Btu/h) of the total input rating of all

– 6 –

Page 6
Image 6
GSW JW727 JWF657, JW717, JW517, JW327 JWF507, JW527 JWF307V, JW317 Air Requirements, Air Supply, In Canada