GSW POWER VENTED GAS FIRED WATER HEATER Air Requirements for Canadian Installations, Required

Models: POWER VENTED GAS FIRED WATER HEATER

1 18
Download 18 pages 18.78 Kb
Page 6
Image 6
Air Requirements for Canadian

-5-

Air Requirements for Canadian

Installations

Canadian Codes allow for the use of a single air supply source. Canadian customers and authorities having jurisdiction may use the sizing listed in Table 1. Check Local Codes.

When using a single air supply, the duct shall terminate within 1 foot (30 cm) above and within 2 feet (60 cm) horizontally from the burner level of the appliance having the largest input as shown in Figure 3 (b), (c) and (d).

An opening shall be located neither more than 18 inches (450 mm), nor less than 6 inches (150 mm), above floor level. See Figure 3 (b), (c) and (d).

Two permanent openings shall be provided connecting the confined space (e.g., closet/small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (5.5 cm²/kW) of all appliances in the confined space. The top opening shall commence within 12" (30 cm) of the top of space and the bottom opening shall commence within 12" (30 cm) of the bottom of the enclosure. See Figure 3

(a).

All exterior vent openings are to be clear of snow levels.

Table 1

Combined Input of All

Required

Acceptable Round

Appliances in Confined

Free Area

Duct Size Diameter

 

Space*

 

 

 

 

 

 

 

 

 

A 1

B 2

 

 

 

 

 

BTU/hr

(KW/hr)

In.2

cm2

In.

mm

In.

mm

 

 

 

 

 

 

 

 

 

25,000

(8)

 

7(45)

 

3(75)

4(100)

 

 

 

 

 

 

 

50,000

(15)

 

7(45)

 

3(75)

4(100)

 

 

 

 

 

 

75,000

(23)

 

11 (70)

4(100)

5(125)

 

 

 

 

 

 

100,000

(30)

 

14(90)

4(100)

5(125)

 

 

 

 

 

 

125,000

(37)

 

18(120)

5(125)

6(150)

 

 

 

 

 

 

150,000

(45)

 

22(140)

5(125)

6(150)

 

 

 

 

 

 

 

 

 

1 Maximum length of ducts in column A is 20 equivalent feet (6.1 meters)

2 Maximum length of ducts in column B is 50 equivalent feet (15.2 meters)

*All appliances refers to and includes those appliances using the same air source. e.g. Water heater, furnace, boiler, clothe dryer, etc.