GSW POWER VENTED GAS FIRED WATER HEATER Venting Instructions, Power Vent Connection

Models: POWER VENTED GAS FIRED WATER HEATER

1 18
Download 18 pages 18.78 Kb
Page 7
Image 7
and each

III)EXHAUST VENTING

IMPORTANT: READ THIS SECTION BEFORE

PROCEEDING.

The Superflueseries is designed to exhaust the products of combustion to the outdoors using a sealed vent pipe system. Required materials and vent sizing are described in Table 2. Refer to figure 6 to determine the exhaust vent termination position.

Plan the layout from the vent terminal back to the water heater. Take into consideration piping position, elbows and support.

Venting Instructions

1.Refer to Figure 5 and Table 2 for vent pipe materials and sizing.

ØUse 45° elbows wherever possible.

ØDo not use 90° “back to back” elbows and do not use street elbows. Maintain 6" (150 mm) of straight section between elbows.

ØCalculate “Equivalent Vent Length” before starting. Do not exceed the values shown in Table 2. Example: The water heater is located 12 feet (4 meters ) from the desired termination point. To reach this, you determine that you need (3) 90° elbows plus about 15 feet (5 meters) of 2" (50 mm) straight section. From Table 2, it is seen that each 2" elbow = 5 equivalent feet (1.5 meters) Therefore this example uses 30 equivalent feet.

ØImportant: When using long runs of vent or when passing through cold or unheated areas condensation of the gases can develop. Provision must be made for a condensate trap or drainage.

2.Measure vent piping and cut to required lengths, Pipes shall be cut at right angles and deburred to ensure a good fit.

3.Dry fit all vent pipes, elbows and fittings before joining any parts with solvent cement. Use only the recommended adhesive for ABS, PVC or CPVC, depending on your

installation. PARTS MUST FIT WITHOUT STRESS

OR BENDING OF ANY SECTION,

connection must overlap a minimum of ½” (15 mm). Caution: solvent cements for plastic piping are flammable. Use only in well ventilated areas and keep away from all sources of ignition.

4.Support the vent piping every 4 feet (1.2 meters) to prevent stress or sagging. DO NOT USE AN ELBOW AS A SUPPORT POINT. Elbows are not designed to carry the weight of the venting system. Use appropriate support straps and vibration isolators on a straight section. IMPROPERLY

SUPPORTED VENTING CAN POSE A SAFETY HAZARD.

5.For long runs of venting, or when passing through cold or unheated areas, condensation can develop. Slope vent pipe to drain through termination outlet. If vertical runs are used, a condensate drain should be provided.

6.At the point where the vent pipe exits the building, drill a 2½” (65 mm) hole for 2" (50 mm) venting or a 3¾” (95 mm) hole for 3" (75 mm) venting). See Figure 5.

CAUTION: BEWARE OF ANY CONCEALED WIRING OR PIPING INSIDE THE WALL.

7.Insert the vent pipe through this hole and secure into position. Connect the vent pipe terminal elbow as shown in Figure 5. Seal around the vent pipe with caulking or silicone once the position is finalized. Ensure that the Debris/Rodent Screen is properly installed.

Power Vent Connection

1.The plastic vent piping connects into the rubber coupling on the blower assembly. See Figure 7. Lightly sand the end of the vent pipe to roughen the outside surface to provide a good mechanical connection with the rubber coupling.

2.Loosen the top clamp on the coupling and insert the end of the vent pipe a full 1¼ “ (35 mm). Check that there is no stress in the vent pipe system caused by twisting or bending.

Do not use glue or sealant at this connection.

3.Tighten top clamp so that the vent pipe is firmly secured in the coupling and is gas tight. Do not over-tighten or cause distortion of the parts.

4.Check that the bottom of the coupling is firmly seated on the blower outlet and that the bottom clamp is also secure.

-7-

Page 7
Image 7
GSW POWER VENTED GAS FIRED WATER HEATER Venting Instructions, Power Vent Connection, Iiiexhaust Venting