Section 2 — Installation

Control system interconnections consist of N1 and N2, and leads 23 and 194. Control system intercon- nection leads must be run in a conduit that is sepa- rate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:

 

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

 

 

 

SIZE

 

 

460 feet (140m)

No. 18 AWG.

 

 

461 to 730 feet (223m)

No. 16 AWG.

 

 

731 to 1,160 feet (354m)

No. 14 AWG.

 

 

1,161 to 1,850 feet (565m)

No. 12 AWG.

 

 

 

 

 

‹2.9.2 GTS-TYPE ATS

If the generator is to be installed with an automatic transfer switch, such as an engineered GTS-type switch, it is necessary to connect the two-wire start control system.

Connect the two-wire start signal from the automatic transfer switch to the automatic start connection, which is located in the middle, on the bottom, inside the control panel. Match wires 178 and 183 in the transfer switch to 178 and 183 on the terminal strip in the control panel. The conductors for the two- wire start circuit must be in their own conduit. (See Section 3.1 for further explanation.)

Liquid-cooled 30 kW Generators

Battery electrolyte fluid is an extremely caus- tic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Do not dispose of the battery in a fire. The battery is capable of exploding.

Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

2.10BATTERY INSTALLATION

DANGER

Standby generators installed with automatic transfer switches will crank and start automati- cally when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, ensure that the 15A and

4A fuses are removed from the control console, the AUTO/OFF/MANUAL switch is set to OFF, and the utility supply to the battery charger is removed before removing or connecting battery cables.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

When replacing batteries, use the same number and type of battery. The recommended batteries are Group 26, 12V negative ground 525 CCA/75 AH mini- mum capacity, or Group 27F, 12V negative ground 600 CCA/90 AH minimum capacity. All batteries must be at 100 percent state-of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the inter- vals specified in Section 4, “Maintenance.” A nega- tive ground system is used. Battery connections are shown on the wiring diagrams. Make sure all batter- ies are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

NOTE:

Damage will result if the battery connections are made in reverse.

2.11 PREPARATION BEFORE START-UP

The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on Pages 2 and 3, as well as all other safety information in this manual, before attempting to operate this (and related) equip- ment.

11

Page 13
Image 13
Guardian Technologies 004988-4 owner manual Battery Installation, Preparation Before START-UP, ‹ 2.9.2 GTS-TYPE ATS

004988-4 specifications

Guardian Technologies 004988-4 is a cutting-edge air purifier designed to create a cleaner and healthier indoor environment. With increasing concerns about air quality in our homes and workplaces, this innovative device provides an effective solution to combat airborne pollutants and allergens.

One of the standout features of the Guardian Technologies 004988-4 is its powerful 4-in-1 filtration system. This system includes a pre-filter that captures larger particles like dust and pet hair, a true HEPA filter that traps 99.97% of particles as small as 0.3 microns, an activated carbon filter that helps reduce odors, and a UV-C light that targets bacteria and viruses. This comprehensive filtration method ensures that the air you breathe is free from harmful contaminants.

Another important characteristic of the Guardian Technologies 004988-4 is its large coverage area. This air purifier is capable of effectively purifying air in rooms up to 300 square feet, making it suitable for bedrooms, living rooms, and office spaces. Its compact and modern design allows it to blend seamlessly with various interior styles, while its lightweight construction makes it easy to move from one room to another.

Additionally, the Guardian Technologies 004988-4 features a quiet operation mode, ensuring that it can run continuously without disrupting daily activities. It also comes equipped with multiple fan speeds, allowing users to customize the airflow based on their preferences and air quality needs. The unit is designed for user-friendly operation, with simple controls that make it easy to switch between modes and adjust settings.

Energy efficiency is another highlight of the Guardian Technologies 004988-4. It is constructed to consume low energy while maintaining high performance, making it an eco-friendly choice for air purification.

In summary, the Guardian Technologies 004988-4 offers a robust combination of features, including a 4-in-1 filtration system, wide coverage area, quiet operation, and energy efficiency. These characteristics make it a reliable and effective air purifying solution that contributes to a healthier indoor environment, promoting overall well-being for users and their families.