29
Installation Manual of Room Air Conditioner
Wiring of indoor unit
Replace cover after wiring.
Pull it out from front.
Pull the cable gently to make sure it is tight.
Insert the cable from outside the wall hole where piping already exist.
Loose terminal screw and insert cable end fully into terminal block, then tighten it
Note: When additional refrigerant is necessary, first purge air out of connecting pipe by external gas,
then drive out the excessive refrigerant by purging method..
Brand new unit is charged 80g more refrigerant than spec. This is only for first installation to purge air
in the indoor unit and connecting pipe.
When piping is longer than 5m, change additional refrigerant specified in this list.
Pipe length
Refrigerant charge(g)
5m 10m 15m
90 180
Wiring of outdoor unit
Pull it out from front.
Insert the cable from inside the wall hole where piping already exist.
Loose terminal screw and insert cable end fully into terminal block, then tighten it
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Note:
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal
blocks. Terminals of same number and same color shall be connected by the same wire.
Incorrect wiring may damage air conditioner's control or cause operation failure.
Electric wiringNote:
Electric wiring must be done by qualified person.
Use copper wire only.
The parameter of the connecting cable is H05RN-F or H07RN-F
-mod 09-12: 3G1.5mm2+1x0.75mm2
-mod 18 : 3G2.5mm2+1x0.75mm2
Indoor unit
Outdoor unit
White
Black
Red
Yellow/Green power
1(N) L
N
2(L) 3(C)
Terminal block
Wire clip
Wire loop