Haier HSU-12HEA03/R2-I Outdoor unit, Installation of Outdoor Unit, Connection of pipes

Models: HSU-18HEA03/R2-I HSU-12HEA03/R2-I HSU-09HEA03/R2-I

1 13
Download 13 pages 46.02 Kb
Page 7
Image 7
Outdoor unit

Outdoor unit

1.Installation of Outdoor Unit

Install according to Drawing for the installation of indoor and outdoor units

2.Connection of pipes

1.Installation of Outdoor Unit To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius should be 30 to 40 mm or longer.

2.Connection of pipes Connecting the pipe of gas side first makes working easier. The connection pipe is specialized for R410A.

Half union

 

 

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spanner

Torque wrench

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Pipe Diameter

Fastening torque

 

 

 

 

Liquid side 6.35mm(1/4")

18N.m

 

 

 

 

Liquid side 9.52mm(3/8")

42 N.m

 

 

 

 

Gas side 12.7mm(1/2")

55N.m

 

 

 

 

Gas side 15.88mm(5/8")

60 N.m

 

 

 

 

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

The standard pipe length ism. If it is over m, the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional refrigerant.

B

Outdoor unit

Indoor unit

A

A

Outdoor unit

B

Indoor unit

A

BOil trap Indoor unit

Outdoor unit

CAUTION

3.Connection Max.Elevation: A1 =10m(for: 09k 12k),

A2=15m(for:18k )

4.Attaching Drain-Elbow In case the elevation A is more than 5m, oil trap shoud be installed every 5~7m

In case A is more than 5m

Max. Length:B1=15m(for: 09k 12k),B2=25m(for:18k )

In case the pipe length B is more than 10m,

the refrigerant should be charged, according to 20 g/m.

3.Connection

Manual background Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into terminal block, then tighten the screws.

Manual background Insert the cable according to terminal number in the same manner as the indoor unit.

4.Attaching Drain-Elbow

Manual background If the drain-elbow is used, please attach it as figure.

Note: Only for heat pump unit.

Manual background If wiring is not correct, proper operation can not be carried out and controller may be damaged.

Manual background Fix the cable with a clamp.

Drain hose

Drain elbow