Haier R410A service manual Fuzzy Operation Outdoor unit H/P Model

Models: R410A

1 109
Download 109 pages 10.99 Kb
Page 76
Image 76

Operation Details

26°C Intake Air Temp => 25°C

24°C Intake Air Temp<26°C => Intake Air Temp+1°C 22°C Intake Air Temp<24°C => Intake Air Temp+0.5°C 18°C Intake Air Temp<22°C => Intake Air Temp

Intake Air Temp<18°C

=> 18°C

When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.

While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper- ature

Fuzzy Operation (Outdoor unit H/P Model)

When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.

When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.

24°C Inatake Air Temp => Fuzzy Operation for Cooling

21°C Inatake Air Temp<24°C => Fuzzy Operation for Dehumidification

Inatake Air Temp<21°C

=> Fuzzy Operation for Heating

If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1)Fuzzy Operation for Cooling

According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.

Compressor ON Temp => Setting Temp+0.5°C Compressor OFF Temp => Setting Temp+0.5°C

At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.

26°C Intake Air Temp => 25°C

24°C Intake Air Temp<26°C => Intake Air Temp+1°C 22°C Intake Air Temp<24°C => Intake Air Temp+0.5°C 18°C Intake Air Temp<22°C => Intake Air Temp

Intake Air Temp < 18°C

=> 18°C

When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.

While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.

2)Fuzzy Operation for Dehumidification

According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.

Compressor ON Temp => Setting Temp+0.5°C Compressor OFF Temp => Setting Temp+0.5°C

Copyright ©2008 LG Electronics. Inc. All right reserved.

- 76 -

Only for training and service purposes

LGE Internal Use Only

 

Page 76
Image 76
Haier R410A service manual Fuzzy Operation Outdoor unit H/P Model