5.If you are using one extension cord for more than one tool, add the nameplate amperes and use the sum to determine the required minimum cord size.
(See Figure C.)
6 . If you are using an extension cord outdoors, make sure it is marked with the suffix
7.Make sure your extension cord is properly wired and in good electrical condition. Always replace a damaged extension cord or have it repaired by a qualified electrician before using it.
8.Protect your extension cords from sharp objects, excessive heat, and damp or wet areas.
RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS* (120 VOLT)
NAMEPLATE |
| EXTENSION CORD LENGTH |
| ||
AMPERES |
|
|
|
|
|
(At Full Load) |
|
|
|
|
|
| 25 | 50 | 75 | 100 | 150 |
| Feet | Feet | Feet | Feet | Feet |
0 – 2.0 | 18 | 18 | 18 | 18 | 16 |
2.1 – 3.4 | 18 | 18 | 18 | 16 | 14 |
3.5 – 5.0 | 18 | 18 | 16 | 14 | 12 |
5.1 – 7.0 | 18 | 16 | 14 | 12 | 12 |
7.1 – 12.0 | 18 | 14 | 12 | 10 | - |
12.1 – 16.0 | 14 | 12 | 10 | - | - |
16.1 – 20.0 | 12 | 10 | - | - | - |
*Based on limiting the line voltage drop to five volts at 150% of the rated amperes.