5.If you are using one extension cord for more than one machine, add the nameplate amperes and use the sum to determine the required minimum cord size.
(See Table A.)
6.If you are using an extension cord outdoors, make sure it is marked with the suffix
7.Make sure your extension cord is properly wired and in good electrical condition.
Always replace a damaged extension cord or have it repaired by a qualified electri- cian before using it.
8.Protect your extension cords from sharp objects, excessive heat, and damp or wet areas.
RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*
(120 or 240 VOLT)
NAMEPLATE |
|
|
|
| EXTENSION CORD LENGTH |
| ||||||||
AMPERES |
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||
(at full load) |
|
|
|
|
|
|
|
|
|
|
| |||
25 Feet |
| 50 Feet |
| 75 Feet |
| 100 Feet | 150 Feet | |||||||
0 – 2.0 | 18 |
| 18 |
| 18 |
| 18 | 16 | ||||||
2.1 | – 3.4 | 18 |
| 18 |
| 18 |
| 16 | 14 | |||||
3.5 | – 5.0 | 18 |
| 18 |
| 16 |
| 14 | 12 | |||||
5.1 | – 7.0 | 18 |
| 16 |
| 14 |
| 12 | 12 | |||||
7.1 – 12.0 | 18 |
| 14 |
| 12 |
| 10 | - | ||||||
12.1 | – 16.0 | 14 |
| 12 |
| 10 |
| - |
| - | ||||
16.1 | – 20.0 | 12 |
| 10 |
| - |
| - |
| - | ||||
TABLE A | * Based on limiting the line voltage drop to five volts at 150% of the rated amperes. | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|