Heat & Glo • 6000GBV, 6000GBV-IPI • 2104-900 Rev. H • 11/08 31
G. Wall Switch Installation for Fan (Optional)
If the box is being wired to a wall mounted switch for use
with a fan (See Figure 12.5):
The power supply for the appliance must be brought into
a switch box.
The power can then be supplied from the switch box to the
appliance using a minimum of 14-3 with ground wire.
• At the switch box connect the black (hot) wire and red
(switch leg) wire to the wall switch as shown.
• At the appliance connect the black (hot), white (neutral)
and green (ground) wires to the junction box as shown.
Add a 1/4 in. insulated female connector to the red (switch
leg) wire, route it through the knockout in the face of the
junction box, and connect to the top fan switch connector
(1/4 in. male) as shown.
WHT
WHT
BLK
BLK
GRNwire
insidebox
Copper
groundattached
toGRN screw with
GRNwire
14/2WG
CoverPlate
outsidefirebox
Romex
Connector
Figure 12.4 Junction Box Detail
NOTICE: DO NOT wire
110 VAC to wall switch.
Red
Switch
SwitchBox
Red
Black
Black
Green Green
White
Power
Supply
Wires
White
Red
Black
Green
White
Minimum14-3 AWG
withGround
JunctionBox
Knockout
Figure 12.5 Junction Box Wired to Wall Switch or BC10
F. Junction Box Installation
If the box is being wired from the INSIDE of the appli-
ance:
Remove the screw attaching the junction box/receptacle
to the outer shell, rotate the junction box inward to dis-
engage it from the outer shell (see Figure 12.4).
Pull the electrical wires from outside the appliance through
the opening into the valve compartment and secure wires
with a Romex connector. See Figure 12.4.
• Make all necessary wire connections to the junction
box/receptacle and reattach the junction box/receptacle
to the outer shell.