Page 8 7014-083E September 1, 2008
R
CB1200-I Pellet Insert
Fire Risk.
Comply with all minimum clear-
ances to combustibles as speci-
fied.
WARNING
Failure to comply may cause
house fire.
NOTE:
• Illustrations reflect typical installations
and are FOR DESIGN PURPOSES
ONLY.
• Illustrations/diagrams are not drawn to
scale.
• Actual installation may vary due to
individual design preference.
B. Clearance To Combustibles, UL and ULC12 in
Rear Shroud
6 in
Shown with Hopper Extended
Optional Outside
Air
Combustible
Mantel
INSTALLED AS A BUILT-IN UNITShown with Rear Vent and Optional Outside AirFigure 8.1
Figure 8.2
AS A BUILT-INB
D
C
E
B
C
A
0 INCH (0mm) CLEARANCETO EXPOSED SECTION AND FACE TRIM
Rear Shroud Kit, Part 811-0680 is Required for Built-In Installation (see pages 17-18 for installation instructions)A Top of Shroud Top Vent 3.0 76
Rear Vent 0 0
B Sides of Inside Shroud Top or Rear Vent 0 0
C Back of Inside Shroud Top Vent 2.5 64
Rear Vent 0 0
D Vent Pipe to Combustible Top or Rear Vent 3.0 76
E From Outside Edge of
Panel Set to Combustibles 0 0
Inches Millime-