E36/39/42 INSTALLATION INSTRUCTIONS
2. Frame the Fireplace
The E Series fireplace will fit the framed opening width shown in the table below x
Figure 5 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All required clearances to combustibles around the fireplace must be adhered to. Any framing across the top of the fireplace must be above the level of the top standoffs. Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney section.
|
|
|
|
| Cat # | A |
|
|
|
|
|
| E/EC36 | 42 in. - 1067 mm |
|
|
|
|
|
| E/EC39 | 45 in. - 1143 mm |
|
|
|
|
|
| E/EC42 | 48 in. - 1219 mm |
|
|
|
|
|
|
|
|
|
Figure 5 - Framing the Fireplace
CLEARANCES!
A minimum 1/2 in. air clearance must be maintained at the back and sides of the fireplace assembly.
Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney section.
WARNING!
Do not apply combustible finishing materials over any part of the black face of this fireplace or a structure fire may result. The black metal fireplace front may only be covered with noncombustible materials such as ce- ramic tile, brick, or stone. Do not cover or block any cooling air slots. Do not cover any portion of the opening to the fireplace that would prevent the installation of an authorized glass door.
08/04 | 17335 Rev L | 11 |