1. Top Vent - Horizontal Termination - (continued)

Two Elbows

WARNING**

Fire Risk.

When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fireplaces, a one foot minimum vertical vent section is required before

installing first elbow.

When using DVP-TB1 termination cap on top vented fireplaces, a three foot minimum vertical vent section is required before installing first elbow.

When using any other cap, a section of vertical pipe (12 inches minimum) MUST be installed prior to attaching a 90° elbow.

Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 7.3).

V1 Minimum**

H1 + H2 Maximum

90 Elbow**

1/2 ft.

152 mm

 

 

 

 

1/2 ft.**

152 mm

1 ft.

305 mm

 

 

 

 

1-1/2 ft.**

457 mm

2 ft.

610 mm

2-1/2 ft.**

762 mm

4 ft.

1.2 m

3-1/2 ft.

1.1 m

6 ft.

1.8 m

 

 

 

 

4-1/2 ft.

1.4 m

14 ft.

4.3 m

 

 

 

 

H1 + H2 Max. =14 ft. (4.3 m)

V1 + H1 + H2 Max. = 40 ft. (12.2 m)

See Warning**

V1

H2

H1

 

INSTALLED

HORIZONTALLY

Figure 7.5