D. ROOFTOP INSTALLATION
1. Before locating the unit on the roof, make sure that the
strength of the roof and beams is adequate at that point
to support the weight involved. This is very important
and user’s responsibility.
2. For rigging and roofcurb details, see Figures 8 and 9.
Use field-furnished spreaders.
3. For roofcurb assembly, see Roofcurb Installation Instruc-
tions.
4. If the roofcurb is not used, provisions for disposing of
condensate water runoff must be provided.
5. The unit should be placed on a solid and level roofcurb
or platform of adequate strength. See Figure 10.
6. The location of the unit on the roof should be such as to
provide proper access for inspection and servicing.
IMPORTANT: If unit will not be put into service immediately,
cover supply and return openings to prevent excessive con-
densation.
FIGURE 8
RIGGING FOR LIFTING
INSTALL GASKET
NAILING STRIP
DUCT FLANGE NOT
TO EXCEED 1" [25.4 mm]
SUPPLY DUCT
RETURN DUCT
CAULK ALL JOINTS
WATERTIGHT
ROOFCURB
UNIT
A0719-02
A0719-03
CORNER WEIGHTS BY PERCENTAGE
ABCD
33% 27% 17% 23%
FIGURE 9
ROOFCURB INSTALLATION
A074403
Illustration
A074403
A0744-03
13